Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 131 of 151 
Ar 12    External air temperaure setpoint for boiler heaters (on)  -50.0 
-58 
110.0 
230 
°C 
°F 
Dec 
int 
Ar 13    Temperature differential for boiler heaters (off)  0.1 
0 
25.0 
45 
°C 
°F 
Dec 
int 
Ar 14    Time delay before turning the boiler on  0  250    Min 
Ar 15    Setpoint for boiler heaters (on) in chiller  -50.0 
-58 
110.0 
230 
°C 
°F 
Dec 
int 
Ar 16    Proportional band for boiler heaters in chiller  0.1 
0 
25.0 
45 
°C 
°F 
Dec 
int 
Ar 17    Setpoint for boiler heaters (on) in HP  -50.0 
-58 
110.0 
230 
°C 
°F 
Dec 
int 
Ar 18    Proportional band for boiler heaters in HP  0.1 
0 
25.0 
45 
°C 
°F 
Dec 
int 
Ar 19    External air setpoint to stop the compressor as integration function  -50.0 
-58 
110.0 
230 
°C 
°F 
Dec 
int 
Ar 20    External air differential to stop the compressor as integration function  0.1 
0 
25.0 
45 
°C 
°F 
Dec 
int 
Ar21  Termoregulation probe anti freeze alarm in chiller mode 
0= Not enabled 
1= Evaporator inlet 
2= Evaporator outlet 1 and 2 
3= Evaporator outlet 1 and 2 and common outlet 
4= External temperature 
0 4     
Ar22  Termoregulation probe anti freeze alarm in heat pump mode 
0= Not enabled 
1= Evaporator inlet 
2= Evaporator outlet 1 and 2 
3= Evaporator outlet 1 and 2 and common outlet 
4= External temperature 
0 4     
Ar23  Termoregulation probe anti freeze alarm water condenser 
0= not enabled. 
1= Condenser common water inlet probe. 
2= Condenser common water inlet and condenser inlet 1 / 2 probe. 
3= Condenser water outlet 1 / 2 probe. 
4= Condenser water outlet 1 / 2 and common outlet 
5= External temperature 
0 5     
Ar24  Water pump / antifreeze alarm in OFF/ stand-by 
0= Aways in OFF 
1= ON only with thermoregulation control 
0 1     
Ar25  Termoregulation probe water pump in antifreeze mode 
0= Not enabled 
1= Evaporator inlet 
2= Evaporator outlet 1 and 2 
3= Evaporator outlet 1 and 2 and common outlet 
4= External temperature 
0 4     
Ar26  Set point starting water pump in antifreeze alarm 
-50.0 
-58 
110.0 
230 
°C 
°F 
Dec 
int 
Ar27  Differential starting water pump in antifreeze alarm 
0.1 
0 
25.0 
45 
°C 
°F 
Dec 
int 
Parameter  Description  min  max  M. u.  Resolution 
dF 1   Defrost configuration: 
0= Not enabled 
1= Start and stop for temperature / pressure 
2= Start depends on probe selected by par. dF24 and stop for time duration 
(dF05) 
3= Start depends on probe selected by par. dF24 and stop for external 
contact 
4= Defrost only with condenser fan 
5= Start from digital input and stop on probe selected by par. dF24  
0 5     
dF 2   Temperature or pressure of the defrost start-up  -50.0 
-58 
0.0 
0 
110.0 
230 
50.0 
725 
°C 
°F 
bar 
psi 
Dec 
int 
Dec 
Int 
dF 3   Temperature or pressure of the defrost stop  -50.0 
-58 
0.0 
0 
110.0 
230 
50.0 
725 
°C 
°F 
bar 
psi 
Dec 
int 
Dec 
Int 
dF 4   Minimum defrost duration.  0  250  Sec   
dF 5   Maximum defrost duration.  0  250  Min   
dF 6   Time delay between the defrost of two circuits  0  250  Min   
dF 7   OFF compressor delay before the defrost  0  250  Sec   
dF 8   OFF compressor delay after the defrost  0  250  Sec   
dF 9   Defrost interval time of the same circuit  1  99  Min   
dF 10    Temperature setpoint for combined defrost of the 1st circuit after parameter 
DF10 counting. 
-50.0 
-58 
110.0 
230 
°C 
°F 
Dec 
int 










