Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 129 of 151 
FA 3   If the condenser fan control is the triac output, when the regulation starts the 
trigger output will drive the condenser fan at the maximum voltage for the time 
FA 3 then, then the regulation will follow the temperature/pressure of the 
probe. 
0 250 Sec   
FA 4   Phase shifting of the fan motor 
0 8 
Micro 
Sec 
250μs 
FA 5   Number of condensing circuits 
0= one condenser circuit 
1= tow condenser circuits 
0 1     
FA 6   Pre-ventilation time before turning on the compressor in chiller mode. 
To turn on the fan at the maximum speed before the compressor and reduce 
the successive condensing temperature/pressure increasing. (only if FA01=4) 
0 250 Sec   
FA 7   Minimum speed for condenser fan in Chiller mode. 
To set the minimum fan speed percentage value (30..100%), it is related to 
the fan power supply. 
0 100  %   
FA 8   Maximum speed for condenser fan in Chiller mode. 
To set the maximim fan speed percentage value (30..100%), it is related to 
the fan power supply. 
0 100  %   
FA 9   Proportional speed control FA01 = 4 
Temperature or pressure limit to enable the minimum speed FA 7 
ON/OFF regulation FA01 = 2/3 
SETpoint step n° 1 
-50.0 
-58 
0.0 
0 
110.0 
230 
50.0 
725 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
FA 10    Proportional speed control FA01 = 4 
Temperature or pressure limit to enable the maximum speed FA 8 
ON/OFF regulation FA01 = 2/3 
SETpoint step n° 2 
-50.0 
-58 
0.0 
0 
110.0 
230 
50.0 
725 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
FA 11    Proportional speed control FA01 = 4 
Proportional band for condenser fan control in chiller 
To set the temperature/pressure differential between the minimum and the 
maximum of the fan speed regulation. 
ON/OFF regulation FA01 = 2/3 
Differential step circuit n° 1 
0.1 
0 
0.1 
1 
25.0 
45 
14.0 
203 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
FA 12    Proportional speed control FA01 = 4 
CUT-OFF differential in chiller. To set a temperature/pressure differential to 
stop the fan. 
ON/OFF regulation FA01 = 2/3 
Differential step circuit n° 2 
0.1 
0 
0.1 
1 
25.0 
45 
14.0 
203 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
FA 13    Over ride CUT- OFF in chiller. To set a temperature/pressure differential to 
keep the minimum fan speed. 
0.1 
0 
0.1 
1 
25.0 
45 
14.0 
203 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
FA 14    CUT-OFF time delay. To set a time delay before activating the CUT-OFF 
function after the fan start-up. 
If after the compressor start-up the proportional regulator requires to turn off 
the fan (cut-off) and FA14≠0, the fan is on at the minimum speed for the time 
set in this parameter. If FA14=0 the function is disabled. 
0 250 Sec  
FA 15    Night speed in chiller. To set the maximum fan speed percentage value 
(30..100%), it is related to the fan power supply. 
0 100  %  
FA 16    Minimum speed for condenser fan in Heat Pump mode. 
To set the minimum fan speed percentage value (30..100%), it is related to 
the fan power supply. 
0 100  %   
FA 17    Maximum speed for condenser fan in Heat Pump mode. 
To set the maximum fan speed percentage value (30..100%), it is related to 
the fan power supply. 
0 100  %   
FA 18    Proportional speed control FA01 = 4 
Temperature or pressure limit to enable the minimum speed FA16 
ON/OFF regulation FA01 = 2/3 
SETpoint step n° 1 
-50.0 
-58 
0.0 
0 
110.0 
230 
50.0 
725 
°C 
°F 
Bar 
Psi 
Dec
int 
Dec 
int 
FA 19    Proportional speed control FA01 = 4 
Temperature or pressure limit to enable the maximum speed FA17 
ON/OFF regulation FA01 = 2/3 
SETpoint step n° 2 
-50.0 
-58 
0.0 
0 
110.0 
230 
50.0 
725 
°C 
°F 
Bar 
Psi 
Dec
int 
Dec 
int 
FA 20    Proportional speed control FA01 = 4 
Proportional band for condenser fan control in heat pump 
To set the temperature/pressure differential between the minimum and the 
maximum of the fan speed regulation. 
ON/OFF regulation FA01 = 2/3 
Differential step circuit n° 1 
0.1 
0 
0.1 
1 
25.0 
45 
14.0 
203 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
FA 21    Proportional speed control FA01 = 4 
CUT-OFF differential in heat pump. To set a temperature/pressure differential 
to stop the fan. 
ON/OFF regulation FA01 = 2/3 
Differential step circuit n° 2 
0.1 
0 
0.1 
1 
25.0 
45 
14.0 
203 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 