Technical data

Ichill 200CX EVO rev 1.1 14/11/2013
Pag. 127 of 151
US 18
Auxiliary relay 2 winter set point
US16 US17
°C
°F
Bar
Psi
Dec
int
Dec
int
US 19
Auxiliary relay 2 summer differential
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
US 20
Auxiliary relay 2 winter differential
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
US 21 Maximum operating time of auxiliary realys 0 250 min
US 22 Auxiliary proportional output n° 1 operating mode
0= Not enabled
1= Always available with direct action
2= Available only when the unit is on with direct action
3= Always available with reverse action
4= Available only when the unit is on with reverse action
0 4
US 23 Analogue input configuration for auxiliary control 1
Allows to select which probe value Pb1..Pb10 controls output
1 20
US 24
Analog output 1 summer minimum set point
-50.0
-58
0.0
0
US26
°C
°F
Bar
Psi
Dec
int
Dec
int
US 25
Analog output 1 summer maximum set point
US26
110.0
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
US 26
Analog output 1 summer set point
US24 US25
°C
°F
Bar
Psi
Dec
int
Dec
int
US 27
Analog output 1 winter minimum set point
-50.0
-58
0.0
0
US29
°C
°F
Bar
Psi
Dec
int
Dec
int
US 28
Analog output 1 winter maximum set point
US29
110.0
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
US 29
Analog output 1 winter set point
US27 US28
°C
°F
Bar
Psi
Dec
int
Dec
int
US 30
Analog output 1 summer differential
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
US 31
Analog output 1 winter differential
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
US 32 Analog output 1 minimum value 0 US33 %
US 33 Analog output 1 maximum value US32 100 %
US 34 Auxiliary proportional output n° 2 operating mode
0= Not enabled
1= Always available with direct action
2= Available only when the unit is on with direct action
3= Always available with reverse action
4= Available only when the unit is on with reverse action
0 4
US 35 Analogue input configuration for auxiliary 2 control
Allows to select which probe value Pb1..Pb10 controls output
1 20
US 36
Analog output 2 summer minimum set point
-50.0
-58
0.0
0
US38
°C
°F
Bar
Psi
Dec
int
Dec
int
US 37
Analog output 2 summer maximum set point
US38
110.0
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
US 38
Analog output 2 summer set point
US36 US37
°C
°F
Bar
Psi
Dec
int
Dec
int