CO 91 Minimum time between to switch on of the compressor 0 250 sec
CO 92 Compressor activation delay starting from water solenoid valve activation 0 250 sec
CO 93 Water solenoid valve de-activation delay starting from compressor de-
activation
0 250 sec
CO 94 % output of the inverter compressor in defrost 1 100 %
CO 95 Free cooling water pump operation time to generate maintenance warning 0 999 10 Hr 10 Hr
CO 96 % output of the inverter compressor in unloading 1 100 %
Parameter Description min max M. u. Resolution
US 1 Auxiliary relay 1 operating mode (See graph and auxiliary relay functions)
0= Not enabled
1= Always available with direct action
2= Available only when the unit is on with direct action
3= Always available with reverse action
4= Available only when the unit is on with reverse action
0 4
US 2 Analog input configuration for auxiliary relay 1 control. Allows to select which
probe value Pb1..Pb10 controls the relay
1 20
US 3
Auxiliary relay 1 summer minimum set point
-50.0
-58
0.0
0
US5
°C
°F
Bar
Psi
Dec
int
Dec
int
US 4
Auxiliary relay 1 summer maximum set point
US5
110.0
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
US 5
Auxiliary relay 1 summer set point
US3 US4
°C
°F
Bar
Psi
Dec
int
Dec
int
US 6
Auxiliary relay 1 winter minimum set point
-50.0
-58
0.0
0
US8
°C
°F
Bar
Psi
Dec
int
Dec
int
US 7
Auxiliary relay 1 winter maximum set point
US8
110.0
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
US 8
Auxiliary relay 1 winter set point
US6 US7
°C
°F
Bar
Psi
Dec
int
Dec
int
US 9
Auxiliary relay 1 summer differential
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
US 10
Auxiliary relay 1 winter differential
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
US 11 Auxiliary relay 2 operating mode (See graph and auxiliary relay functions)
0= Not enabled
1= Always available with direct action
2= Available only when the unit is on with direct action
3= Always available with reverse action
4= Available only when the unit is on with reverse action
0 4
US 12 Analogue input configuration for auxiliary relay 2 control . Allows to select
which probe value Pb1..Pb10 controls the relay
1 20
US 13
Auxiliary relay 2 summer minimum set point
-50.0
-58
0.0
0
US15
°C
°F
Bar
Psi
Dec
int
Dec
int
US 14
Auxiliary relay 2 summer maximum set point
US15
110.0
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
US 15
Auxiliary relay 2 summer set point
US13 US14
°C
°F
Bar
Psi
Dec
int
Dec
int
US 16
Auxiliary relay 2 winter minimum set point
-50.0
-58
0.0
0
US18
°C
°F
Bar
Psi
Dec
int
Dec
int
US 17
Auxiliary relay 2 winter maximum set point
US18
110.0
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int