Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 125 of 151 
CO 47    Unloading Differential. From temperature / pressure in HP mode (See 
unloading function). 
0.1 
0 
0.1 
1 
25.0 
45 
14.0 
203 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
CO 48    Maximum unloading duration time from temperature/pressure control.  1  250  Min   
CO 49    Number of steps for circuit with active unloading 
1= 1st step 
2= 2nd step 
3= 3rd step 
1 3     
CO 50    Minimum ON time of the capacity step after the unloading function start (only 
for capacity compressor) 
0 250 Sec    
CO 51    Setpoint of the solenoid valve (on) of the liquid injection  0 
32 
150 
302 
°C 
°F 
Dec / int 
int 
CO 52    Setpoint of the solenoid valve (off) of the liquid injection  0.1 
0 
25.0 
45 
°C 
°F 
Dec 
int 
CO 53    Maximum time of work in neutral zone without insert resource  0  250  Min  10 Min 
CO 54    Maximum time of work in neutral zone without rotation resource  0  999  Hr  1Hr 
CO 55    Set point unloading compressor from low evaporator water temperature 
-50.0 
-58 
110.0 
230 
°C 
°F 
Dec 
int 
CO 56    Differential unloading compressor from low evaporator water temperature 
0.1 
0 
0.1 
1 
25.0 
45 
14.0 
203 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
CO 57    Maximum unloading duration time from low evaporator water temperature 
0 250 Min   
CO 58    maximum time pump-down in stopped 
CO58 = 0 Not enabled 
0 250 Sec    
CO 59    maximum time pump-down in started 
CO59 = 0 Not enabled 
0 250 Sec    
CO 60    Maximum time start up compressor inverter controlled 
0 250 sec   
CO 61    Minimum value proportional output from start up compressor 
0 100 %   
CO 62    Minimum time capacity variation from start up compressor inverter controlled 
0 250 sec   
CO 63    Minimum percentage continuative of work of the compressor inverter 
controlled before to start counting CO64 time 
0 100 %   
CO 64    Maximum time continuative of work of the compressor with percentage less of 
CO63 
0 250 Min  10 Min 
CO 65    Time of forcing the compressor inverter controlled to the maximum power 
0 250 sec  sec 
CO 66    Maximum time continuative of work of the compressor inverter controlled 
0 999 Hr  1Hr 
CO 67    Minimum value of the compressor 1 inverter controlled 
1 CO68 %   
CO 68    Maximum value of the compressor 1 inverter controlled  CO67  100  %   
CO 69    Minimum value of the compressor 2 inverter controlled  1  CO70  %   
CO 70    Maximum value of the compressor 2 inverter controlled  CO69  100  %   
CO 71    Minimum time capacity variation compressor inverter controlled  1  250  sec   
CO 72    Maximum operating time of a single compressor 
0 250 Min 
CO 73    Sanitary water pump hour counter  0  999  10 Hr  10 Hr 
CO 74    Solar panel water pump hour counter  0  999  10 Hr  10 Hr 
CO 75    Forced time to reverse the 4 way valve when the compressor is switched off  0  250  sec   
CO 76    Maximum number of compressors to use in Chiller  1  15     
CO 77    Maximum number of compressors to use in Heat pump  1  15     
CO 78    Maximum number of compressors to use in Sanitary water  1  15     
CO 79    Maximum % output of the inverter compressor in Chiller  1  100  %   
CO 80    Maximum % output of the inverter compressor in Heat pump  1  100  %   
CO 81    Maximum % output of the inverter compressor in Sanitary water  1  100  %   
CO 82    Outside temperature to reduce inverter compressor speed in Heat pump  -50.0 
-58 
0.0 
0 
110.0 
230 
50.0 
725 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
CO 83    Hysteresis temperature to reduce inverter compressor speed in Heat pump  0.1 
0 
0.1 
1 
25.0 
45 
14.0 
203 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
CO 84    Compressor speed if outside temperature > CO82  0  100  %   
CO 85    Evaporator water pump OFF time if the set point is reached  0  250  10 min   
CO 86    Evaporator water pump OFF time if the machine is STD-BY or OFF  0  250  10 Ore   
CO 87    Evaporator water pump ON time  0  250  Sec  10sec 
CO 88    Condenser water pump OFF time if the set point is reached  0  250  10 min   
CO 89    Condenser water pump OFF time if the machine is STD-BY or OFF  0  250  10 Ore   
CO 90    Condenser water pump ON time  0  250  Sec  10sec 










