Technical data

Ichill 200CX EVO rev 1.1 14/11/2013
Pag. 119 of 151
CF 53 Proportional output OUT 4
0= not configured
1= modulation evaporator water pump 0÷10V
2= Free cooling modulating output 0÷10V
3= not used
4= auxiliary output AUX1 0÷10V
5= auxiliary output AUX2 0÷10V
6= inverter compressor 1 0÷10V
7= inverter compressor 2 0÷10V
8= modulating condenser fan circuit 1 0÷10V
9= modulating condenser fan circuit 2 0÷10V
10= modulating condenser fan circuit 1 PWM
11= modulating condenser fan circuit 2 PWM
o1..c50 ON / OFF output with the same meaning of relè
0
o 1
11
c50
CF 54 Remote keyboard 1 configuration
0= Not enabled
1= Enabled model with ambient temperature sensor
2= Enabled model without ambient temperature sensor
0 2
CF 55 Remote Panel 2 configuration
0= Not enabled
1= Enabled model with ambient temperature sensor
2= Enabled model without ambient temperature sensor
0 2
CF 56 Offset of the probe of the remote terminal 1 -12.0
-21
12.0
21
°C
°F
Dec
int
CF 57 Offset of the probe of the remote terminal 2 -12.0
-21
12.0
21
°C
°F
Dec
int
CF 58 Icon function
0=
chiller / heat pump
1=
chiller / heat pump
0 1
CF 59 0= Chiller / Heat pump selection by keyboard
1= Chiller / Heat pump selection by digital input
2= Chiller / Heat pump selection by analogue input
0 2
CF 60 Automatic change over setpoint for chiller/ heat pump selection (CF79 = 2) -50.0
-58
110.0
230
°C
°F
Dec
int
CF 61 Automatic change over differential (CF79 = 2) 0.1
0
25.0
45
°C
°F
Dec
int
CF 62 °C or °F selection
0= °C / °BAR
1= °F / °psi
0 1
CF 63 Power supply frequency
0= 50 Hz
1= 60 Hz
2= Vcc power supply
(ATTENTION
When CF83 = 2 the proportional outputs for fan control are not enabled)
0 2
CF 64 Serial address 1 247
CF 65 Firmware Release (only reading) Sola lettura
CF 66 Eeprom parameter map (only reading) Sola lettura
CF 67 Compressor 1 capacity 0 100%
CF 68 Compressor 2 capacity 0 100%
CF 69 Compressor 3 capacity 0 100%
CF 70 Compressor 4 capacity 0 100%
CF 71 Not used 0 0
CF 72 Not used 0 0
CF 73 Maximum number of start up of the compressor in 15 minutes
0= Not enabled
0 15
CF 74 Working mode of the compressor
0 = chiller and heat pump
1 = only chiller
2 = only heat pump
0 2
CF 75 Enable hybrid exchangers 0 1
CF 76 Buzzer presence (0=disabled, 1=enabled) 0 1
CF 77 Chiller operation (1=only compressor; 2=only Free cooling; 3=compressors
and Free cooling)
1 3
CF 78 Enable I/O expansion
0= not enabled
1= enabled
0 1
CF 79 Enable expansion valve 1
0= not enabled
1= enabled
0 1
CF 80 Enable expansion valve 2
0= not enabled
1= enabled
0 1