Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 114 of 151 
48.2  Alarm: Circuit Alarm 
Alarm 
Code 
Alarm description  Compressors 
of the circuit 
 (n) 
Compressors 
of the other 
circuit 
Fan condensing of 
the circuit (n) 
Fan condensing 
of the other 
circuit 
b(n)HP 
High pressure switch of the circuit (n)  OFF   
OFF after 60 seconds 
b(n)LP  Low pressure switch of the circuit (n) 
OFF 
OFF 
b(n)AC 
Anti-freeze in chiller of the circuit (n)  OFF 
OFF 
b(n)AH 
Anti-freeze in heat pump of the circuit (n)  OFF 
OFF 
b(n)hP  High condensing pressure of the circuit (n) 
OFF 
OFF after 60 seconds   
b(n)hP  High condensing temperature from NTC of the circuit (n) 
OFF 
OFF after 60 seconds   
b(n)LP 
Low condensing pressure - (evaporating with low pressure transducer) 
with transducer of the circuit of the (n) 
OFF 
OFF 
b(n)lP 
Low condensing temperature NTC circuit (n)  OFF  OFF   
b(n)tF  Fan overload circuit (n) 
OFF 
OFF 
b(n)PH  Pump down alarm in stop regulation of the circuit (n) 
OFF 
OFF 
b(n)PL 
Pump down in regulation start-up of the circuit (n) 
OFF 
OFF 
b(n)dF 
Bad defrost circuit (n)  
b(n)Cu 
Unloading from condenser high temp/press of the circuit (n)  
b(n)Cu  Unloading from evaporator low temp/press of the circuit (n) OFF  
OFF 
b(n)rC  Recovery function disabled in circuit (n)  
b(n)ds 
Circuit (n) disabled from keyboard  OFF   
OFF 
b(n)Ac  Anti-freeze circuit (n) message in chiller     
b(n)Ah  Anti-freeze circuit (n) message in heat pump     
(n) identifies the circuit 1 or 2 
48.3  Alarm: Compressor Alarm 
Alarm 
Code 
Alarm description  Compressor 
(n) 
Compressors not involved 
C(n)HP 
Compressor(n) high pressure switch  OFF   
C(n)oP 
Compressor(n) oil pressure switch / Oil level switch  OFF   
C(n)tr 
Compressor(n) overload  OFF   
C(n)dt 
Compressor high discharge temperature  OFF   










