Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 111 of 151 
For some alarms is possible to set a number of alarms per hour:
•  if the alarm occours a number of time lower than the value set, the alarm is automatic reset
•  if the alarm occours a number of time equal the value set, the alarm is manual reset
Each hour is divided in 16
th
 intervals (each interval is 3600 / 16 = 225 seconds). 
1°Int 2°Int 3°Int 4°Int 5°Int 6°Int  7°Int 8°Int 9°Int 10°Int 11°Int 12°Int 13°Int 14°Int 15°Int 16°Int
After the unit start-up, each interval is marked as “not active”. During the interval counting, for 255seconds, if 
at least an alarm event appears, the interval itself is marked “Active”. 
Starting from the first interval the instrument calculates the 16 intervals and, at the end, it restats overwriting 
from the first. 
In this way the last hour is always monitored and counted the active intervals. when the number of active 
intervals reaches the threshold set with the corresponding parameter the alarm becomes manual. 
By setting the threshold (parameter)=0 the alarm is manual from its first activation while if the threshold=16 
the alarm is always automatic . 