Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 110 of 151 
Reset 
Automatic when the communication is working 
Restart 
Automatic 
Symbol 
 blinking 
Action 
Alarm relay + buzzer ON 
Regolatori 
Loads 
OFF 
AUAL Failed Communication With Electronic Expansion Valve 
Label on alarm 
visualization menu 
AUAL 
Origin 
Failed communication with electronic expansion valve 
Reset 
Automatic when the communication is working 
Restart 
Automatic 
Symbol 
 blinking 
Action 
Alarm relay + buzzer ON 
Regolatori 
Loads 
OFF 
b1UA, b2UA Expansion valve 1 or Expansion Valve 2 Alarm 
Label on alarm 
visualization menu 
b1UA (expansion valve 1 alarm) 
b2UA (expansion valve 2 alarm) 
Origin 
When the electronic expansion valve is on alarm 
Reset 
Automatic when the alarm is solved 
Restart 
Automatic 
Symbol 
 blinking 
Action 
Alarm relay + buzzer ON 
Regolatori 
Loads 
Load of the circuit OFF 
Alarm relay and buzzer 
Alarm relay / buzzer outputs 
Origin 
Alarms still active 
Alarms not reset 
Reset relay alarm 
Whitout alarms 
In stand- by or remote ON-O FF if AL42 = 1 
Buzzer silencing 
By pushing one of the key of the front panel 
The alarm relay is enabled only by configurating the corresponding output resource. 
Keyaboard Alarm 
Label on alarm 
visualization menu 
keyaboard Alarm description 
noL 
No data communication between the keyaboard 
and the regulator. 
48. MANUAL ALARM PROCEDURE 
CONCEPT OF NUMBER OF EVENTS PER HOUR 