Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 107 of 151 
Origin  Only in defrost if DF01 = 1,3 (defrost en temperature/pressure or external 
contact): when the defrost ends after the DF05 timeout. 
Reset 
  Stand - by or remote ON-OFF. 
  Next defrost ends for temperature/pressure. 
Restart 
Automatic if next defrost ends for temperature/pressure, otherwise manual. 
Symbol 
On the display the symbol 
 is blinking 
Action 
Alarm relay + buzzer OFF 
b1Cu – b2Cu Unloading disabled from High condensing temperature / pressure in chiller 
Label on alarm 
visualization menu 
b1CU (unloading high temperature from condenser of the circuit 1) 
b2CU (unloading high temperature from condenser of the circuit 2) 
Origin  When the temperature/pressure of condenser probe control is higher then 
CO44 
Reset    When the temperature/pressure of condenser probe is lower than CO44 –
CO45 (differential) 
  After unloading is activated and after Par. CO47 
Restart 
Automatic 
Symbol 
On the display the symbol 
 is blinking 
Action 
Alarm relay + buzzer OFF 
b1Cu – b2Cu: Unloading from low condensing temperature / pressure in Heat pump 
Label on alarm 
visualization menu 
b1CU (unloading message from condenser 1) 
b2CU (unloading message from condenser 2) 
Origin  During normal running condition when the temperature/pressure of 
evaporator/condenser probe is lower than < CO46 setpoint 
Reset    when the temperature/pressure of evaporator/condenser probe value is 
higher than CO46 + CO47 
  After unloading is activated and after Par. CO48 
Restart 
Automatic 
Symbol 
On the display the symbol 
 is blinking 
Action 
Alarm relay + buzzer OFF 
b1rC – b2rC recovery disabled from high condensing temperature/pressure in Chiller 
Label on alarm 
visualization menu 
b1rC (recovery disabled message from circuit 1) 
b2rC (recovery disabled message from circuit 2) 
Origin  In normal running condition when the temperature/pressure probe value is 
higher than the set rC06 
Reset    When the temperature/pressure probe value is lower than the rC06 –
rC07(differential) 
  Unloading start after the time delay Par. rC08 
Restart 
Automatic 
Symbol 
On the display the symbol 
 is blinking 
Action 
Alarm relay + buzzer OFF 
b1PH - b2PH: Pump Down stop alarm from pressure switch / Low pressure switch 
Label on alarm 
visualization menu 
b1PH (Pump down stop alarm of the circuit 1) 
b2PH (Pump down stop alarm of the circuit 2) 
Origin  Pressure switch: if CO36 = 1,2,3,4 and ID not active, the pump down stops 
because of the timeout CO39. 
Transducer: if CO36 = 1,2,3,4 and the set CO37 is not reached: the pump 
stops because of the timeout CO39. 