Technical data

Ichill 200CX EVO rev 1.1 14/11/2013
Pag. 107 of 151
Origin Only in defrost if DF01 = 1,3 (defrost en temperature/pressure or external
contact): when the defrost ends after the DF05 timeout.
Reset
Stand - by or remote ON-OFF.
Next defrost ends for temperature/pressure.
Restart
Automatic if next defrost ends for temperature/pressure, otherwise manual.
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer OFF
b1Cu – b2Cu Unloading disabled from High condensing temperature / pressure in chiller
Label on alarm
visualization menu
b1CU (unloading high temperature from condenser of the circuit 1)
b2CU (unloading high temperature from condenser of the circuit 2)
Origin When the temperature/pressure of condenser probe control is higher then
CO44
Reset When the temperature/pressure of condenser probe is lower than CO44 –
CO45 (differential)
After unloading is activated and after Par. CO47
Restart
Automatic
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer OFF
b1Cu – b2Cu: Unloading from low condensing temperature / pressure in Heat pump
Label on alarm
visualization menu
b1CU (unloading message from condenser 1)
b2CU (unloading message from condenser 2)
Origin During normal running condition when the temperature/pressure of
evaporator/condenser probe is lower than < CO46 setpoint
Reset when the temperature/pressure of evaporator/condenser probe value is
higher than CO46 + CO47
After unloading is activated and after Par. CO48
Restart
Automatic
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer OFF
b1rC – b2rC recovery disabled from high condensing temperature/pressure in Chiller
Label on alarm
visualization menu
b1rC (recovery disabled message from circuit 1)
b2rC (recovery disabled message from circuit 2)
Origin In normal running condition when the temperature/pressure probe value is
higher than the set rC06
Reset When the temperature/pressure probe value is lower than the rC06 –
rC07(differential)
Unloading start after the time delay Par. rC08
Restart
Automatic
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer OFF
b1PH - b2PH: Pump Down stop alarm from pressure switch / Low pressure switch
Label on alarm
visualization menu
b1PH (Pump down stop alarm of the circuit 1)
b2PH (Pump down stop alarm of the circuit 2)
Origin Pressure switch: if CO36 = 1,2,3,4 and ID not active, the pump down stops
because of the timeout CO39.
Transducer: if CO36 = 1,2,3,4 and the set CO37 is not reached: the pump
stops because of the timeout CO39.