Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 105 of 151 
Regulation 
Compressor 
OFF 
Other loads 
Not modified 
C1HP - C2HP - C3HP - C4HP compressor high pressure alarms 
Label on alarm 
visualization menu 
C1HP ( compressor 1 high pressure alarm) – … C4HP (compressor 4 high 
pressure alarm) 
Origin 
The unit is running and the digital input of the compressor high pressure switch 
is active 
Reset 
Digital input not active 
Restart 
Reset procedure in Menu function 
Reset procedure in Menu function 
Always manual AL54 = 0 
Always automatic AL54 =16 
From manual to utomatic if AL54 value is between 1 and 15 
Symbol 
On the display the symbol 
 is blinking 
Action 
Alarm Relay + and buzzer on 
Regulation 
Condensing fan  If FA02=0 the fan is forced at maximum speed for 60 seconds then switched 
off 
If FA02=1 the fan is forced at maximum speed for 60 seconds then regulate 
according to normal fan regulation 
C1oP - C2oP - C3oP - C4oP - Pressure switch alarm / compressor oil 
Label on alarm 
visualization menu 
C1oP (Compressor 1pressure switch … C4oP (Compressor 4 pressure switch)
Origin 
The alarm is not signalled: during the AL01 delay after turning on the 
compressor, during the AL12 delay that starts after the AL11 delay when the 
unit is properly running 
Reset 
Digital input not active 
Restart 
Automatic - Manual after AL013 events per hour (Reset procedure in Menu 
function). 
If AL76=1 the alarm is only a warning and the compressor remains on 
Symbol 
On the display the symbol 
 is blinking 
Action 
Alarm Relay + and buzzer on 
OIL ALARM FROM PRESSOSTAT SWITCH OR OIL LEVEL SWITCH (screw) 
Occasionally it is possible to find both the safety systems, the delay, the active input duration and the 
number of events per hour allow to set-up both the protections. 
Par. AL11 Oil alarm delay after on compressor. 
It allows to set a time delay before signalling the oil or the oil level switch alarms after the on compressor. 
Par. AL12 Duration of the pressure switch / oil level switch in normal operating conditions. 
Duration of the oil level switch activation during normal running condition. 
It allows to set the time delay before signalling the alarm. AL11 defines the delay counting, it helps to 
override the low pressure or the low oil level determined, for example, by a new partialization step of the 
compressor itself. 
Par. AL13 Maximum number of alarm events per hour. 
It determs the maximum number of alarm events before switching the restart from automatic to manual. 
C1Pd - C2Pd – compressor oil differential pressure 
Label on alarm 
visualization menu 
C1Pd (compressor 1) 
C2Pd (compressor 2) 










