Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 103 of 151 
b1AH - b2AH Anti-freeze alarm / Low outlet air temperaure(Air/Air unit only) on heat pump 
mode 
Label on alarm 
visualization menu 
b1AH (anti-freeze alarm of the circuit #1 in heat pump) 
b2AH (anti-freeze alarm of the circuit #2 in heat pump) 
b1Ah (anti-freeze alarm signalling of the circuit #1 in heat pump) 
b2Ah (anti-freeze alarm signalling of the circuit #2 in heat pump) 
Both the labels are displayed when the alarm is coming from the evaporator 
inlet probe or evaporator common outlet probe or when there is only one digital 
input configured. 
Origin 
Normal conditions, stand-by, remote OFF: when the anti-freeze probe value is 
lower than AL33 for AL36 seconds. 
With the anti-freeze digital input is active. 
Reset 
When the anti-freeze probe value is higher than AL33 + AL34. 
With digital input ont active 
Restart  Automatic – Manual after AL37 events per hour (Reset procedure in Menu 
function). 
If AL74=1 to reset the alarm is necessary to type the password 
Symbol 
On the display the symbol 
 is blinking 
Action  If AL38=0 only the compressors are turned off and than display shows b1Ah - 
b2Ah, the buzzer and the alarm relay are not activated. 
If AL38=0 only the compressors are turned off and than display shows b1AH - 
b2AH, the buzzer and the alarm relay are activated. 
If the alarm comes from the digital input also the anti-freeze heaters are turned 
on. 
Attention 
Par. AL35 anti-freeze alarm delay (low outlet air temperature air/air unit) when the unit starts in heat pump 
mode. 
In stand-by or remote OFF: there is an anti-freeze alarm and the time delay in AL35>0, if the unit is manually 
turned on in heat pump from keyboard or remote input, the alarm is reset so the unit can start at least for the 
time set in AL35 in order to heat the water or the air. After the AL35 delay if the anti-freeze probe is still lower 
than AL33 setpoint for AL36 seconds the unit is locked again with an anti-freeze alarm. 
 b1hP - b2hP High pressure / Condensing High temperature of the Circuit 
Label on alarm 
visualization menu 
b1hP (high pressure digital input of the circuit #1) 
b2hP (high pressure digital input of the circuit #2) 
Origin 
In chiller or heat pump, if the condensing probe is higher than AL09 setpoint.
Reset 
If the condensing probe value is lower than AL09 –AL10 (differential) 
Restart 
Reset procedure in Menu function. 
Always manual AL54 = 0 
Always automatic AL54 =16 
From manual to utomatic if AL54 value is between 1 and 15 
Symbol 
On the display the symbol 
 is blinking 
Action 
Alarm Relay + and buzzer on 
Regulation 
Condensing fan  If FA02=0 the fan is forced at maximum speed for 60 seconds then switched 
off 
If FA02=1 the fan is forced at maximum speed for 60 seconds then regulate 
according to normal fan regulation 
b1LP - b2LP low pressure switch circuit #1 or 2 
Label on alarm 
visualization menu 
b1LP (low pressure switch circuit #1) 
b2LP (low pressure switch circuit #2) 