Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 102 of 151 
Restart 
Reset procedure in Menu function 
Always manual AL54 = 0 
Always automatic AL54 =16 
From manual to utomatic if AL54 value is between 1 and 15 
Symbol 
On the display the symbol 
 is blinking 
Action 
Alarm Relay + and buzzer on 
Regulation 
Condensing fan  If FA02=0 the fan is forced at maximum speed for 60 seconds then switched 
off 
If FA02=1 the fan is forced at maximum speed for 60 seconds then regulate 
according to normal fan regulation 
b1lp - b2lp Low temperature / Low Condensing pressure of the Circuit 
Label on alarm 
visualization menu 
b1lP (low pressure digital input of the circuit 1) 
b2lP (low pressure digital input of the circuit 2) 
Origin 
When the condensing probe value is lower than AL03 setpoint if: 
•  In chiller or heat pump 
•  Stand-by o remote OFF when AL08 = 1 
•  In defrost when AL06=1  
The alarm is not signalled if: 
•  In defrost ,for the time AL07, when the 4-way valve is turned on. 
•  For the time set in AL01 after turning on the compressor. 
Reset  When the condensing probe temperature is higher than AL03 + AL04 
(differential) 
Restart  Automatic– Manual after AL05 events per hour (Reset procedure in Menu 
function). 
Symbol 
On the display the symbol 
 is blinking 
Action 
Alarm Relay + and buzzer on 
b1AC - b2AC - b1Ac - b2Ac Antifreeze alarm / Low outlet temperature (Air / Air unit in Chiller 
mode) 
Label on alarm 
visualization menu 
b1AC (anti-freeze alarm of the circuit #1 in chiller) 
b2AC (anti-freeze alarm of the circuit #2 in chiller) 
b1Ac (anti-freeze alarm signalling of the circuit #1 in chiller) 
b2Ac (anti-freeze alarm signalling of the circuit #2 in chiller) 
Both the labels are displayed when the alarm is coming from the evaporator 
inlet probe or evaporator common outlet probe or when there is only one digital 
input configured. 
Origin 
Normal conditions, stand-by, remote OFF: when the anti-freeze probe value is 
lower than AL26 for AL28 seconds. 
With the anti-freeze digital input is active. 
Reset 
When the anti-freeze probe value is higher than A26+ AL27(differential) 
With the anti-freeze digital input is active. 
Restart  Automatic – Manual after AL29 events per hours (Reset procedure in Menu 
function). 
If AL74=1 to reset the alarm is necessary to type the password 
Symbol 
On the display the symbol 
 is blinking 
Action  If AL30=0 only the compressors are turned off and than display shows b1Ac 
b2Ac, the buzzer and the alarm relay are not activated. 
If AL30=0 only the compressors are turned off and than display shows b1Ac 
b2Ac, the buzzer and the alarm relay are activated. 
If the alarm comes from the digital input also the anti-freeze heaters are turned 
on. 