To reset the NG Series Industrial Wireless Gateway IPv4 address by using the A-coded M12 auxiliary power
connector:
1. If in a non-hazardous environment connect pin 2 to pin 3 (white to blue wire) until the status
indicator starts flashing between green and amber.
2. Maintain the connection for approximately 5 seconds.
3. The status indicator should start flashing between amber and red indicating that the IPv4 address
has been reset to factory default (“192.168.1.1”).
Remove the magnet or auxiliary power reset connection within 10 seconds of starting the process to
prevent the device from entering the factory default restore process.
Restore Factory Defaults
To use a magnet to restore the gateway to the factory default settings:
1. Place a magnet against the magnet icon located on the NG Series Gateway until the status
indicator starts flashing between green and amber.
2. Hold the magnet in place for 15 seconds while the status indicator flashes between amber and
red to start the factory default restoration process. The status indicator will indicate steady red
once the restore factory defaults process starts.
3. After a few minutes the TCP/IP IPv4 address will be reset to factory default (“192.168.1.1”), all
user configurations will revert to the factory default and device software will be reverted to the
factory installed version.
Alternatively, if in a non-hazardous environment, use the auxiliary power connection reset option by
connecting pin 2 to pin 3 (white to blue wire) until the status indicator starts flashing between amber and
red. Remove the connection after 15 seconds.
Note!