NG Series Industrial Wireless Gateway device managers limit the number of field devices connected to
the gateway. This could be any combination of “IO”, “Router” or “Router IO” devices up to a total of 50
devices. Up to 9 child devices may connect to each router enabled device. The maximum number of hops
between the NG Series Industrial Wireless Gateway and a VP Series 2000 field device should be limited to
4.
Move the Device or Gateway
Relocating a field device or reorienting its axis or orientation relative to the gateway as little as 6 cm (2
1/3 inch), or one-half of a 2.4 GHz wavelength, may improve signal strength.
Change Gateway
Change the gateway deployment by:
• Using the authorized 6dBi higher gain antenna on the gateway. Verify that the resulting narrowly
focused radio frequency distribution pattern meets your needs. OR
• Add gateways.
Verify Signal Strength
Check that the devices' signal strength are within guidelines. Use your NG Series Industrial Wireless
Gateway web interface to monitor device signal strength and packet error rates. Signal strength (RSSI)
should be above -85 dBm, and preferably above -78 dBm.
Validate Device Data
Using the NG Series Industrial Wireless Gateway device manager web-interface, verify the publication
status and that the measurements are displayed in the “Readings” tab.
Icon
Status
Description
Wireless signal icon with a cross
Not Joined
Device is not visible to the network.
It may be out of range, is restarting or is off.
Wireless Signal Icon
Joining
Device is busy negotiating to join the network.
Bold Wireless Signal Icon
Joined
Device joined and configuring.
Wireless Signal Icon with a tick
mark
Joined and
Publishing
Device configured and publishing PV data.
Initial publication of measurements may take some time after devices have joined the network. After the
initial period, during which the network is forming, measurements will be published at
1-minute intervals.
Use the data trend tab after selecting a VP Series 2000 sensor in the device tree to view a history of the
selected parameters.