User's Guide
Table Of Contents
- General Safety
- Hardware
- Network Design
- Installation and Configuration
- Install Battery
- Configure Network
- VP Series 2000 Configuration Software
- Provision Devices
- Before you Begin
- Device Sleep State
- Provision Using a USB NFC Reader
- Provision Using a Divigraph ISA100 Gateway
- Provision Using a Yokogawa ISA100 Gateway
- Provision Using a Honeywell ISA 100 Gateway
- Provision using an Emerson WirelessHART Gateway
- Unprovision Devices
- Unprovision Using a USB NFC Reader
- Unprovision Using a Yokogawa ISA100 Gateway
- Unprovision Using a Honeywell ISA100 Gateway
- Reboot the Device
- Configure Devices
- System 1 Installation and Configuration
- Mount Devices
- Verification
- Maintenance
- Monitor Battery Levels
- Battery Status Monitoring
- Clean and Inspect Devices
- Update Device Firmware
- Update Radio Firmware
- Troubleshooting VP Series 2000 Devices
- Harden the System
EVR-VPXDOC-0036 VP Series 2000 User Guide
DIVIGRAPH
Rev 2.4.1
September 2021
Proprietary & Confidential – Copyright © 2020 Divigraph (Pty) Ltd. All Rights Reserved 44
Open the Device
Open the device to replace or inspect the battery as well as to inspect the
interior components such as the O-rings and device electronic contacts.
! Note
Before opening the device, remove it from the field and operating
environment.
To prevent damage to the O-rings, turn the e-module retaining ring
counterclockwise ½ to one turn, and then clockwise about ¼ turn, and
repeat until the sensor body O-ring is exposed.
Refer to the “Install Battery” section for more information regarding how to
open VP Series 2000 devices.
If you have trouble removing the retaining ring, the e-module may be
rotating with the retaining ring. Turn the retaining ring clockwise slightly and
press down lightly on the e-module to hold it in place. Then turn the
retaining ring counterclockwise.
Inspect the E-Module
Remove the e-module by pressing upward lightly on the side opposite the
module’s contact pins.
To ensure that the e-module (top of the device) remains in good operating condition:
• Visually check that the enclosure, battery terminal spring, and contact pins are undamaged.
• Inspect the e-module positive battery terminal spring. Look for chemical corrosion or deposits.
• Verify that the e-module contact pins move freely when pressed against the sensor module contact
pads.
• Visually check that the e-module housing is not cracked or otherwise degraded.
Inspect the Battery
Before removing the battery with the battery installation tool, look for signs of battery leakage.
! CAUTION
CORROSIVE CHEMICAL HAZARD
If a battery has leaked, do not touch the corrosive electrolyte.