Storage Status
Good
The E-Module internal storage is working as expected.
Warning
A problem has occurred with the device internal storage. Contact Divigraph
technical support for assistance.
Bootloader Status
Good
The E-Module bootloader is working as expected.
Upgrade Error
An application firmware upgrade error has occurred. Upgrade the device
application firmware.
No Upgrade Found
No application firmware found. Upgrade the device firmware.
Launch Error
Unable to start the device application firmware. Upgrade the device firmware.
Sensor Status
Good
The sensor has been detected and is working correctly.
Read Warning
(Identification)
The sensor identification data could not be read.
Model
Unrecognized
The sensor identification data was successfully read but the model is not
recognized.
Model
Unsupported
The sensor identification data was successfully read but the model is not
supported.
Bypass
(Identification)
The sensor identification data was successfully read but the model has been
detected as a legacy model.
Read Warning
(Calibration)
The sensor calibration data could not be read.
Bypass
(Calibration)
The sensor calibration data was successfully read but the model has been
detected as a legacy model.
Read Warning
(Diagnostics)
The sensor diagnostics data could not be read.
Bypass
(Diagnostics)
The sensor diagnostics data was successfully read but the model has been
detected as a legacy model.
Read Warning
(Temperature)
The sensor detected a temperature read fault.
Read Warning
(Accelerometer)
The sensor detected an accelerometer read fault.
If any sensor warning occurs, contact Divigraph technical support for assistance.
Temperature Min, Max
If the sensor temperature has been read successfully the maximum and minimum detected
temperatures are displayed.
Vibration Max X, Y, Z
If the sensor vibration values have been read successfully the maximum overall vibration recorded for
each axis is displayed.