User's Guide
Table Of Contents
- General Safety
- Hardware
- Network Design
- Installation and Configuration
- Install Battery
- Configure Network
- VP Series 2000 Configuration Software
- Provision Devices
- Before you Begin
- Device Sleep State
- Provision Using a USB NFC Reader
- Provision Using a Divigraph ISA100 Gateway
- Provision Using a Yokogawa ISA100 Gateway
- Provision Using a Honeywell ISA 100 Gateway
- Provision using an Emerson WirelessHART Gateway
- Unprovision Devices
- Unprovision Using a USB NFC Reader
- Unprovision Using a Yokogawa ISA100 Gateway
- Unprovision Using a Honeywell ISA100 Gateway
- Reboot the Device
- Configure Devices
- System 1 Installation and Configuration
- Mount Devices
- Verification
- Maintenance
- Monitor Battery Levels
- Battery Status Monitoring
- Clean and Inspect Devices
- Update Device Firmware
- Update Radio Firmware
- Troubleshooting VP Series 2000 Devices
- Harden the System
EVR-VPXDOC-0036 VP Series 2000 User Guide
DIVIGRAPH
Rev 2.4.1
September 2021
Proprietary & Confidential – Copyright © 2020 Divigraph (Pty) Ltd. All Rights Reserved 39
Phase 3 VP Series 2000 WirelessHART Devices
The device variable IDs listed below are used when mapping WirelessHART VP Series 2000 device
variables to Modbus registers.
Devices use firmware version 3.1.2.1 or later.
Byte Order: Refer to WirelessHART network hardware vendor documentation.
Data type: float (4-bytes)
• Burst Message 0
o [0] – TEMPERATURE - 0 - Primary Variable (PV)
o [1] - Z OVL ACC - 1 - Secondary Variable (SV)
o [2] - Z OVL VEL - 2 - Tertiary Variable (TV)
o [3] - Z PK DEMOD - 3 - Quartenary Variable (QV)
o [4] - Y OVL ACC - 4
o [5] - Y OVL VEL - 5
o [6] - X OVL ACC - 6
o [7] - X OVL VEL - 7
• Burst Message 1
o [0] - BATTERY LIFE (DAYS LEFT) - 243
o [1] - NOT USED - 250
o [2] - NOT USED - 250
o [3] - NOT USED - 250
o [4] - NOT USED - 250
o [5] - NOT USED - 250
o [6] - NOT USED - 250
o [7] - NOT USED – 250