User's Guide
Table Of Contents
- General Safety
- Hardware
- Network Design
- Installation and Configuration
- Install Battery
- Configure Network
- VP Series 2000 Configuration Software
- Provision Devices
- Before you Begin
- Device Sleep State
- Provision Using a USB NFC Reader
- Provision Using a Divigraph ISA100 Gateway
- Provision Using a Yokogawa ISA100 Gateway
- Provision Using a Honeywell ISA 100 Gateway
- Provision using an Emerson WirelessHART Gateway
- Unprovision Devices
- Unprovision Using a USB NFC Reader
- Unprovision Using a Yokogawa ISA100 Gateway
- Unprovision Using a Honeywell ISA100 Gateway
- Reboot the Device
- Configure Devices
- System 1 Installation and Configuration
- Mount Devices
- Verification
- Maintenance
- Monitor Battery Levels
- Battery Status Monitoring
- Clean and Inspect Devices
- Update Device Firmware
- Update Radio Firmware
- Troubleshooting VP Series 2000 Devices
- Harden the System
EVR-VPXDOC-0036 VP Series 2000 User Guide
DIVIGRAPH
Rev 2.4.1
September 2021
Proprietary & Confidential – Copyright © 2020 Divigraph (Pty) Ltd. All Rights Reserved 36
Static Process Variable Data
Process Variable (PV) or direct data is used to trend the overall vibration and temperature. PV data can
be sent to System 1 through GCI, HART-IP, Modbus or OPC. PV data sent by GCI conforms to the ISA100,
foundation fieldbus standard. Data sent by HART-IP conforms to the HART standard.
For ISA100 devices PV data is timestamped by the gateway and not at the time of acquisition.
WirelessHART device PV data is timestamped by the device at the time of acquisition.
A user can select the units, sub-units, time interval, Fmin and Fmax settings..
Measurement
Type
Default
Mode
Measurement
Units
Default
Sub-units
(RMS or Peak)
Default Fmin
(high pass filter
frequency)
Default Fmax
(low pass filter
frequency)
Temperature
Enabled
°F, °C
N/A
N/A
N/A
Acceleration
Overall
Enabled
g, m/s^2
(default: g)
RMS
X: 5
Y: 5
Z: 5
X: 5000
Y: 5000
Z: 10000
Velocity
Overall
Enabled
mm/s, inches/s
RMS
X: 5
Y: 5
Z: 5
X: 5000
Y: 5000
Z: 10000
PeakDemod
Overall
Enabled
N/A
Peak
N/A
N/A
Dynamic Data
Dynamic data is measured at the interval and start date/time set by the user. You can select the number
of samples, Fmin, Fmax, and time interval. Dynamic data is collected sequentially for each measurement
axis and time stamped when the data collection occurs.
Measurement
Type
Default
Mode
Measurement
Units
Default Fmin
(high pass filter
frequency)
Default Fmax
(low pass filter
frequency)
Other
Acceleration
Waveforms
Enabled
g, m/s^2
(default: g)
N/A
N/A
Measurement
samples used:
4096
Velocity
Spectrum
(rms only sub-
units)
Enabled
mm/s, inches/s
X: 5
Y: 5
Z: 5
X: 1000
Y: 1000
Z: 1000
Lines Default
FFT Points:
1600
PeakDemod
Spectrum
(Peak only
sub-units)
Enabled
(Z axis only)
g, m/s^2
(default: g)
X: 5
Y: 5
Z: 5
1000
Lines Default
FFT Points:
1600