User's Guide
Table Of Contents
- General Safety
- Hardware
- Network Design
- Installation and Configuration
- Install Battery
- Configure Network
- VP Series 2000 Configuration Software
- Provision Devices
- Before you Begin
- Device Sleep State
- Provision Using a USB NFC Reader
- Provision Using a Divigraph ISA100 Gateway
- Provision Using a Yokogawa ISA100 Gateway
- Provision Using a Honeywell ISA 100 Gateway
- Provision using an Emerson WirelessHART Gateway
- Unprovision Devices
- Unprovision Using a USB NFC Reader
- Unprovision Using a Yokogawa ISA100 Gateway
- Unprovision Using a Honeywell ISA100 Gateway
- Reboot the Device
- Configure Devices
- System 1 Installation and Configuration
- Mount Devices
- Verification
- Maintenance
- Monitor Battery Levels
- Battery Status Monitoring
- Clean and Inspect Devices
- Update Device Firmware
- Update Radio Firmware
- Troubleshooting VP Series 2000 Devices
- Harden the System
EVR-VPXDOC-0036 VP Series 2000 User Guide
DIVIGRAPH
Rev 2.4.1
September 2021
Proprietary & Confidential – Copyright © 2020 Divigraph (Pty) Ltd. All Rights Reserved 20
6. Select the CF file compatible with the devices displayed in the “Device Tag” field.
7. For each type of VP Series 2000 device, modify these Concentrator OID:11 Read Parameters:
OID Concentrator Value
NR1210 Repeater
VP2010 Single Axis
VP2030 Tri-Axis
Update policy
Periodic
Periodic
Periodic
Publication period
0 (zero)
150
150
Stale limit
Default
5
5
Retry mode
Normal
Normal
Normal
8. For each type of VP Series 2000 device, verify these additional Concentrator OID:11 Read
Parameters:
OID Parameter
NR1210 Repeater
VP2010 Single Axis
VP2030 Tri-Axis
UAPMO Diag_Status
To prevent session timeout, select the UAPMO Diag_Status
parameter (if displayed) and click the "<" button. The parameter
is moved to the list of Available Parameters.
AI_01 AI_02 AI_03
AI_04 AI_05 AI_06
AI_07 AI_08
Not available
AI_01 - AI_05:
available
AI_06 - AI_8:
unavailable
AI_01 - AI_08:
available
9. For each type of VP Series 2000 device, configure the Concentrator OID:12 Read Parameters:
OID Concentrator Value
NR1210 Repeater
VP2010 Single Axis
VP2030 Tri-Axis
Update policy
Default
Periodic
Periodic
Publication period
Default
10
10
Stale limit
Default
10
10
Retry mode
Default
Normal
Normal
10. Restart the devices that you changed. Select the “Download” button. The “Error Check” dialog box is
displayed.
11. Click “OK”. The “Download Configuration” dialog box is displayed.
12. Click the check box next to each device you need to restart. Click “Start Download”. Restarting a
device may take one to five minutes.