Install Instructions

LIMITS & REQUIREMENTS OF USE:
H-CLASS
1) H-CLASS HURRICANE PAD - FOR ALL COUNTIES WITH A MAXIMUM WIND SPEED UP TO 150 M.P.H.
TO THICKNESS
(
in
)
= 4
2) THE PAD AND THE SUPPORTED EQUIPMENT MUST BE LOCATED AT GROUND LEVEL. THIS TABLE DOES NOT APPLY TO ROOFTOP EQUIPMENT,
PAD MODEL# WEIGHT WIDTH LENGTH
EQUIPMENT LOCATED ON BALCONIES, OR ANY OTHER EQUIPMENT TO BE ELEVATED ABOVE GROUND LEVEL.
H1840-4 92 18 40
3) THE AREA UNDER CONCERETE SLAB ON GROUND SHALL HAVE ALL MATERIALS REMOVED PRIOR TO INSTALLATION ON COMPACTED SOIL AS VERIFIED
H2424-4 50 24 24
BY OTHERS. MINIMUM SOIL COEFFICIENT OF FRICTION = 0.25
H2436-4 70 24 36
PAD
4) MAXIMUM DIMENSIONS AND WEIGHT OF UNIT / EQUIPMENT SHALL CONFORM TO SPECIFICATIONS STATED HEREIN. PAD WEIGHT TO BE VERIFIED BY OTHERS.
H3030-4 70 30 30
5) O.E.M. INSTALLATION INSTRUCTIONS (INCL. O.E.M. CLIPS) SUPERSEDE HURRICANE PAD INSTALLATION INSTRUCTIONS & USE OF HC-1 CLIPS, IF MORE STRINGENT.
H3060-4 135 30 60
6) ELECTRICAL GROUND, WHEN REQUIRED, TO BE DESIGNED & INSTALLED BY OTHERS. ALL MECHANICAL SPECIFICATIONS (CLEAR SPACE, TONNAGE, ETC.)
H3232-4 87 32 32
SHALL BE AS PER MANUFACTURER RECOMMENDATIONS AND ARE THE EXPRESS RESPONSIBILITY OF THE CONTRACTOR.
H3345-4 125 33 45
7) THE ROLE OF THIS ENGINEER FOR THIS PROJECT IS THAT OF SPECIALTY ENGINEER AND NOT THE ENGINEER OF RECORD.
H3434-4 94 34 34
CONSEQUENTLY, THE ARCHITECT/ENGINEER OF RECORD SHALL BE RESPONSIBLE FOR THE INTEGRITY OF ALL SUPPORTING
H3636-4 100 36 36
SURFACES TO THIS DESIGN WHICH SHALL BE COORDINATED BY THE PERMITTING CONTRACTOR.
H3642-4 117 36 42
8) ENGINEER SEAL AFFIXED HERETO VALIDATES STRUCTURAL DESIGN AS SHOWN. USE OF THIS SPEC. BY CONTRACTOR, et.
H3648-4 133 36 48
al. INDEMNIFIES & SAVES HARMLESS THIS ENGINEER FOR ALL COST & DAMAGES INCLUDING LEGAL FEES & APPELLATE
H3652-4 140 36 52
FEES RESULTING FROM MATERIAL FABRICATION, SYSTEM ERECTION, CONSTRUCTION PRACTICES BEYOND
H3842-4 158 38 42
THAT WHICH IS CALLED FOR BY LOCAL, STATE, & FEDERAL CODES & FROM DEVIATIONS OF THIS PLAN.
H3852-4 145 38 52
9) THIS ENGINEER SHALL NOT BE HELD RESPONSIBLE/LIABLE IN ANY WAY FOR ERRONEOUS OR INACCURATE DATA
H3865-4 170 38 65
OR MEASUREMENTS. DIMENSIONS ARE SHOWN TO ILLUSTRATE DESIGN FORCES AND OTHER DESIGN CRITERIA.
H4040-4 140 40 40
THEY MAY VARY SLIGHTLY, BUT MUST REMAIN WITHIN THE LIMITATIONS SPECIFIED HEREIN.
H4242-4 145 42 42
10) THIS DOCUMENT IS GENERIC AND DOES NOT PERTAIN TO ANY SPECIFIC PROJECT SITE.
H4558-4 180 45 58
11) PADS / UNITS INSTALLED DIRECTLY ON ANY COASTLINE REQUIRE A HEAVIER
H5557-4 240 55 57
AND LARGER PAD TO ACCOUNT FOR EXPOSURE D ; Table 28.3-1; Kz = 1.03
ZH4272
*
234 42 72
12) ALL OTHER UNITS NOT SHOWN SHALL BE DESIGNED ON A CASE BY CASE BASIS.
ZH5890*
*
360 58 90
13) ALTERATIONS OR ADDITIONS TO THIS DOCUMENT ARE NOT PERMITTED AND INVALIDATE THIS CERTIFICATION.
14
)
EXCEPT AS EXPRESSLY PROVIDED HEREIN, NO ADDITIONAL CERTIFICATIONS OR AFFIRMATIONS ARE INTENDED.
)
15) PADS ARE CONSTRUCTED WITH PRECAST CONCRETE, MINIMUM COMPRESSIVE STRENGTH, f'c=7,000 PSI AT 28 DAYS.
16) THIS ENGINEER SHALL BE GIVEN AN OPPORTUNITY TO RE-EVALUATE THIS WORK UPON DISCOVERY OF INACCURATE
INFORMATION PRIOR TO MODIFICATION OF EXISTING FIELD CONDITIONS AND FABRICATION AND INSTALLATION OF MATERIALS.
ENGINEERING DATA:
1) ANALYSES PER 6th EDITION (2017) FLORIDA BUILDING CODE - SECTION 1620 HIGH VELOCITY HURRICANE ZONES.
2) WIND LOADS & LOAD COMBINATIONS PER ASCE 7-10 SECTION 2.4.1 (LOAD COMBINATIONS), SECTION 29.5 & FIGURE 29.5.1 FOR: WIND LOADS ON OTHER STRUCTURES. Wind Speed V = 150 MPH
3) EQUIP. TO BE ANCHORED TO PAD USING (8) DIVERSITECH HC-1 (OR O.E.M. CLIPS) CENTER ALL EQUIPMENT ON PADS. ATTACH CLIPS TO EQUIP (22 GAGE METAL MIN) WITH F = qz*G*Cf*Af (Eq. 29.5-2) = 49.07 *Af (lbs)
1/4" BLUE / WHITE OR STAINLESS TAPCON CONCRETE ANCHORS WITH MINIMUM OF 1" EMBEDMENT. MINIMUM TAPCON SPECIFICATION: 700 LB PULLOUT / 900 LB SHEAR. qz = 0.00256*Kz*Kzt*Kd*V^2 = 44.06 PSF
4) ALL EQUIPMENT REQUIRING TWO PADS ARE TO USE (12) TOTAL HC-1 CLIPS, FOUR (4) PER LENGTH AND TWO (2) PER WIDTH. Exposure C ; Table 28.3-1 Kz = 0.85
5)
RISK CATEGORY
=
II TABLE 1604.5
-
RISK CATEGORY OF BUILDINGS AND OTHER STRUCTURES, SECTION 301.15 OF THE MECHANICAL CODE, WIND RESISTANCE, AND 553.844 OF THE FLORIDA STATUTES STORM LOSS MITIGATION.
Figure 26.8
-
1Kzt
=
1.00
WIND LOAD CALCS:
5)
RISK
CATEGORY
II
TABLE
1604.5
RISK
CATEGORY
OF
BUILDINGS
AND
OTHER
STRUCTURES,
SECTION
301.15
OF
THE
MECHANICAL
CODE,
WIND
RESISTANCE,
AND
553.844
OF
THE
FLORIDA
STATUTES
STORM
LOSS
MITIGATION.
Figure
26.8 1
Kzt
1.00
DiversiTech Corporation
Table 26.6-1 Kd = 0.90
6650 Sugarloaf Parkway #100
* INDICATES TWO H3642-4 PADS ** INDICATES TWO H4558-4 PADS Figure 29.5-1 Cf = 1.31
Duluth, GA 30097 (800) 397-4823
USED IN A 42" x 72" SHAPE USED IN A 58" x 90" SHAPE G = 0.85
R
EQUIPMENT HURRICANE H-CLASS PAD USED
150 MPH 0.6
UNIT+
O
MINIMUM
PAD PAD PAD WIND 0.6
(
WIND PAD
)
RESISTING
W
WEIGHT
MODEL WEIGHT WIDTH LENGTH THICK LOAD MOMENT
)
WEIGHT MOMENT
# WIDTH LENGTH HEIGHT LBS. NUMBER LBS. IN. IN. IN. LBS. FT-LBS. LBS. FT-LBS.
1 13.0 35.0 20.0 89 H3060-4 135 30 60 4.0 239 168
135
168 OK FOR 150 MPH
2 13.0 35.0 20.0 282 H1840-4 92 18 40 4.0 239 168
224
168 OK FOR 150 MPH
UNIT / EQUIPMENT
MAXIMUM DIMENSIONS
INCHES
DESIGN
CHECK
SPECIAL PAD CONFIG.
3 13.0 35.0 22.0 129 H3060-4 135 30 60 4.0 263 198
159
198 OK FOR 150 MPH
4 13.0 35.0 22.0 348 H1840-4 92 18 40 4.0 263 198
264
198 OK FOR 150 MPH
5 13.0 35.0 24.0 172 H3060-4 135 30 60 4.0 287 230
184
231 OK FOR 150 MPH
6 13.0 35.0 24.0 420 H1840-4 92 18 40 4.0 287 230
307
230 OK FOR 150 MPH
7 23.2 23.2 25.4 88 H3060-4 135 30 60 4.0 200 167
134
167 OK FOR 150 MPH
8 23.2 23.2 25.4 153 H3030-4 70 30 30 4.0 200 167
134
167 OK FOR 150 MPH
9 23.2 23.2 28.7 99 H3648-4 133 36 48 4.0 227 208
139
209 OK FOR 150 MPH
10 23.2 23.2 28.7 132 H3636-4 100 36 36 4.0 227 208
139
209 OK FOR 150 MPH
11 24.8 24.8 28.7 108 H3652-4 140 36 52 4.0 243 223
149
223 OK FOR 150 MPH
12 24.8 24.8 28.7 148 H3636-4 100 36 36 4.0 243 223
149
223 OK FOR 150 MPH
13 25.8 25.8 25.4 101 H3345-4 125 33 45 4.0 223 186
136
186 OK FOR 150 MPH
14 25.8 25.8 25.4 178 H3030-4 70 30 30 4.0 223 186
149
186 OK FOR 150 MPH
15 25.8 25.8 28.7 86 H3842-4 158 38 42 4.0 252 232
147
232 OK FOR 150 MPH
16 25.8 25.8 28.7 158 H3636-4 100 36 36 4.0 252 232
155
232 OK FOR 150 MPH
17 25.8 25.8 32.4 76 H4558-4 180 45 58 4.0 284 287
153
288 OK FOR 150 MPH
18 25.8 25.8 32.4 148 H4040-4 140 40 40 4.0 284 287
173
288 OK FOR 150 MPH
19 25.8 25.8 32.4 133 H3865-4 170 38 65 4.0 285 287
182
288 OK FOR 150 MPH
20 25.8 25.8 32.4 220 H3636-4 100 36 36 4.0 285 287
192
288 OK FOR 150 MPH
21
29 3
33 0
39 8
150
H5557 4
240
55
57
40
448
536
234
536
OK FOR
150
MPH
21
29
.
3
33
.
0
39
.
8
150
H5557
-
4
240
55
57
4
.
0
448
536
234
536
OK
FOR
150
MPH
22 29.3 33.0 39.8 297 H4558-4 180 45 58 4.0 448 536
286
536 OK FOR 150 MPH
23 31.0 55.0 27.0 297 H3865-4 170 38 65 4.0 506 443
280
443 OK FOR 150 MPH
24 31.0 55.0 31.0 306
ZH4272*
234 42 72 4.0 581 567
324
567 OK FOR 150 MPH
25 31.2 31.2 25.4 80 H3842-4 158 38 42 4.0 270 226
143
226 OK FOR 150 MPH
PAGE 1 OF 4