Product Overview
2021 Technical Data Sheet
CONDENSATE MANAGEMENT
Product
Condensate Pumps
CP Series Condensate Pumps
Application
Condensate removal for HVAC/R equipment
Purpose
This product Is designed to automatically evacuate condensate or
water discharge from HVACR equipment up to 22' vertically once
the condensate in the reservoir reaches a specified level.
Advantages
Asurity
TM
CP-22 series pumps beat the industry standard of 20’ lift
height by 2 feet and come with innovative features such as:
vibration dampening feet and motor mounts, metal mounting tabs,
four inlet holes (and 3 poly covers for the unused), LED indicators,
float switch and duckbill-style check valve, and detailed installation
instructions. Two terminals are provided allowing the installer
flexibility to connect air-handler shut-down, an important safety
consideration. CP-22 is available with 20’ of 3/8” tubing as well.
Utilizing the same great features but in a low-height (4-3/8”) design,
the CP-22LP is great for tight spaces.
Maximum Condensate Temperatures
• Continuous duty 140°F
• Maximum inlet temperature 160°F
• Not suitable for contact with steam or gases that exceed
160°F
Rated Voltage
120VAC / 230VAC / 60hHz
Rated Current Draw
• 1.9 Amps (120VAC)
• 1.0 Amps (230VAC)
Input Type
• USA 3-prong molded plug (120VAC)
• NEMA 6-15 (230VAC)
Maximum Lift Height
• CP-22 series: 22’
(Every Asurity
TM
condensate pump is computer tested to ensure
excellent performance at all pumping levels.)
Flow Rate @ Zero Head
• CP-22: 1.6 gallons per minute
Dimensions
• CP-22: 11.8” x 5.9” x 6.7” (4.9” low profile)
• CP-22: 5 lbs. (4.7 lbs. low profile)
Inlet Height from Base
• CP-22: 4.4” (1.75” low profile)
Tank Capacity
• CP-22: 1/2 gallon
• CP-22LP: 3/8 gallon