Install Instructions

PROBLEM POSSIBLE CAUSE CORRECTIVE ACTION
Unit does not
start when
full of
condensate
1. Power is not
supplied to pump.
2. Pump impeller is
not turning.
1. Ensure that power is supplied to pump. A
green LED indicator on top of pump cover
will show that power is supplied and that
pump is ready.
2. Clear any blockage in impeller housing.
If problem persists, motor is stuck. Return
pump to place of purchase if under
warranty.
Condensate is
overowing
from unit
1. Power is not
supplied to pump.
2. Pump is in overow
condition.
3. Pump is not level.
4. Outlet ow is
blocked.
5. Pump impeller is
not turning.
1. Ensure that power is supplied to pump. A
green LED indicator on top of pump cover
will show that power is supplied.
2. The inlet ow to condensate pump is
exceeding outlet ow. Check to ensure
that pump safety switch (alarm circuit)
is connected to A/C/furnace unit. The
safety switch connection will shut o A/C /
furnace in this condition.
3. Check to ensure that pump is level. If
pump is not level, it may not activate,
causing water to overow from tank.
Place unit on a at and level surface.
4. Check outlet tubing to ensure that it is not
kinked or blocked. Clear blocked tubing
of slime and debris. Clean inlet and outlet
piping.
5. Clear any blockage in impeller housing.
If problem persists, motor is stuck. Return
pump to place of purchase if under
warranty.
Pump will not
shut o
1. The pump is
in overow
condition.
2. Outlet ow is
blocked.
1. The inlet ow to condensate pump is
exceeding outlet ow. Check to ensure
that pump safety switch (alarm circuit)
is connected to A/C / furnace unit. The
safety switch connection will shut o A/C /
furnace in this condition.
2. Check outlet tubing to ensure that it is not
kinked or blocked. Clear blocked tubing
of slime and debris. Clean inlet and outlet
piping.
Troubleshooting/Dépannage/Solución de
problemas