05: ECO voltage range setting
Interface
Setting
Parameter 2: Set the acceptable high voltage point and
low voltage point for ECO mode by pressing Down key or Up
key.
HLS: High loss voltage in ECO mode in parameter 2.
The setting range in parameter 3 is from +3V to +12V of the
nominal voltage. (Default: +6V)
LLS: Low loss voltage in ECO mode in parameter 2.
The setting voltage in parameter 3 is from -3V to -12V of the
nominal voltage. (Default: -6V)
06: Bypass enable/disable when UPS is off
Interface
Setting
Parameter 2: Enable or disable Bypass function. You may
choose the following two options:
ENA: Bypass enable
DIS: Bypass disable (Default)
07: Bypass voltage range setting
Interface
Setting
Parameter 2: Set the acceptable high voltage point and
acceptable low voltage point for Bypass mode by pressing
the Down key or Up key.
HLS: Bypass high voltage point
120-140: setting the high voltage point from 120Vac to
140Vac. (Default: 132Vac)
LLS: Bypass low voltage point
85-115: setting the low voltage point from 85Vac to
115Vac. (Default: 85Vac)
08: Bypass frequency range setting
Interface
Setting
Parameter 2: Set the acceptable high frequency point and
acceptable low frequency point for Bypass mode by pressing
the Down key or Up key.
HLS: Bypass high frequency point
For 50Hz output frequency models:
51-55Hz: setting the frequency high loss point from 51Hz
to 55HZ. (Default: 53.0Hz)
For 60Hz output frequency models:
61-65Hz: setting the frequency high loss point from 61Hz
to 65Hz. (Default: 63.0Hz)
LLS: Bypass low Frequency point
For 50Hz output frequency models:
45-49Hz: setting the frequency low loss point from 45Hz to