Operation Manual
- 30 -
0DT829 15/10/2012
49E
17 14 12 11 0 0 0 1 1 2 3 4 6 8 9 20 41
17 14 12 11 0 0 0 1 1 2 3 4 6 8 9 20 41
INPUTS
Command Function Description
1 2
N.O
Automatic closing
Permanently closing the contact enables automatic closing.
1 3 N.O
Opening
With DIP1=ON the closure of the contact activates an opening operation.
Step-by-step
With DIP1=OFF the closure of the contact activates an opening or closing
operation in the following sequence: open-stop-close-open.
Note: if automatic closing is enabled, the stop is not permanent but at a
time that is set by the TC.
1 4
N.O
Closing
The closing manoeuvre starts when the contact is closed.
1 6 N.C
Reversal safety
device
Opening the safety contact triggers a reversal of the movement (reopening)
during a closing operation.
41 8 N.C
Reversal safety
device
Opening the safety contact triggers a reversal of the movement (reopening)
during a closing operation.
1 9 N.C
Stop
Opening the safety contact stops the current operation.
1 9 N.O
Non-pulse command
Permanently opening the safety contact enables the operation by non-
pulse command.
In this state, the opening (1-3/1-20) and closing (1-4) controls function only
if held in the pressed position, and the automation stops when the controls
are released.
All safety switches, the step-by-step control and the automatic closing
function are disabled.
1 20 N.O
Partial opening
The closing of the contact activates a partial opening operation of the
duration set with the RP trimmer.
Once the automation stops, the partial opening control performs the
opposite operation to the one performed before stoppage.
0 11
N.C
Closure limit switch
The opening of the limit switch contact stops the closure operation.
0 12
N.C
Opening limit switch
The opening of the limit switch contact stops the opening operation.
0 17
Do not use
Leave the input not connected
Operation by non-pulse command Operation by pulse command
OUTPUTS
Card Output Value Description
EL07L
1 +
0 –
24 V= / 0,5 A
Accessories power supply.
Power supply output for external accessories, including
automation status lamp.
0 14
24V= / 50 W
(2 A)
Flashing light (LAMPH).
Activated during opening and closing operations.
EL07PW1
- LK + 24 V= / 0,5 A Output activated during the door running.
400 V~ / 4 A
Note: if the direction of rotation of the motor is incorrect for the
desired direction of movement, swap the U - W phases.
U W V
M
3 ~