Display Description Selections
available
OT - Selection of type of obstacle
00 - Overcurrent or gate stopped
01 - Overcurrent
02 - Door stopped
CR - Stroke estimate correction [%]
DO NOT USE (diagnostic purposes only)
SM - Selection of operating mode of device connected to terminals
1-6
00 - During the operation, the opening of the safety contact stops the
movement (with disengagement if
/ ).
01 - During the operation, the opening of the safety contact stops the
movement (with disengagement if
/ ). When the
contact closes again, the interrupted operation is resumed.
02 - During the operation, the opening of the safety contact stops the
movement (with disengagement if
/ ). When the
contact closes again, an opening operation is performed.
03 - During the closing operation, the opening of the safety contact
reverses the movement. During the opening operation, the safety
device is ignored.
04 - During the opening operation, the opening of the safety contact
stops the movement (with disengagement if
/ ).
When the contact closes again, the interrupted opening operation
is resumed. During the closing operation, the safety device is
ignored.
05 - During the closing operation, the opening of the safety contact
stops and reverses the movement. During the opening operation,
the opening of the safety contact stops the movement (with
disengagement if
/ ).
TN - Setting of intervention temperature for NIO electronic an-
ti-freeze system and automatic HS ramps [°C]
This value does not refer to the ambient temperature, but to the in-
ternal control panel temperature.
10
HS - Automatic ramp adjustment
ON - Enabled
OF - Disabled
When enabled (ON), at low ambient temperatures the start time
increases
up to the maximum value and the acceleration time
and diminishes to
the minimum value.
NB: for correct operation, the control panel must be exposed to the same am-
bient temperature as the motors.
The intervention temperature can be set via the selection
.
TB - Permanent display of the internal control panel temperature
[°C]
WO - Setting of pre-ashing time on opening [s]
Adjustment of the lead time for the switch-on of the flashing light,
in relation to the start of the opening operation from a voluntary
command.
00 - Minimum
05 - Maximum
00
AP