Installation Instructions
28
IP2246EN
i
NB: make adjustments gradually and only after performing at least three complete
operations to allow the control panel to be set correctly and detect any friction during
operations.
11.5 Second level menu - RO (Radio Operations)
Display Description
SR - Remote control storage
You can directly access the Remote control storage menu even with the display turned
off, but only with the Display visualisation mode option set to 00 or 03:
- for transmitting a remote control not present in the memory;
- for transmitting an unstored channel of a remote control already present in the memo-
ry.
→ →→
→
→
→
...x2, x3...
WARNING: if the display shows flashing, the remote control may already be
stored.
TX - Visualisation of counter showing remote controls stored
→→ → 16 radiocomandi [esempio]
MU - Indication of maximum number of remote controls that can
be stored in the integrated memory
You can store a maximum of 100 or 200 remote control codes.
→→
→
2” 2”
oppure
20 - 200 remote controls that can be stored
10 - 100 remote controls that can be stored
Selections
available
WARNING: selecting → (200 remote controls), the configurations and
saved with the → command will be lost. This also applies for the last configura-
tion reloaded with . In addition, new configurations cannot be saved on and .
Display Description
OL - Indicator light for automation open
00 - proportional flashing depending on the point where the gate wings are positioned and
the operation direction (in battery mode, the flashing is different)
01 - fixed ON (automation not closed)
02 - output active with automation not open
03 - output active with automation closed
04 - output active with automation open
05 - output active with automation moving
06 - output active with automation opening
07 - output active with automation closing
08 - output active with maintenance alarm triggered
09 - output active for indicating batteries almost flat
ON - output always active
16 remote controls (example)
or
BARO - Radio operations