Installation Instructions
21
IP2246EN
11.2 Second level menu - AT (Automatic Configurations)
Display Description
Selections
available
AS - Automation selection
This selection pre-sets the type of motor and a sub-set of param-
eters linked to the kinematic mechanism of the automation for a
standard installation.
See "Selection of automation type", paragraph 11.3.
Each parameter can still be modified when necessary.
NW - Selection of the number of gate wings
In the case of automations with a single gate wing, connect motor
1.
H0 - Predefined setting, residential use 0
This selection loads predefined values for certain standard parameters:
AC - enabling of automatic closing : 1-2
C5 - step-by-step/opening command operation : step-by-step
RM - remote control operation : step-by-step
AM - AUX plug-in board operation : step-by-step
SS - Selection of automation status at start-up : open
H1 - Predefined setting, residential use 1
This selection loads predefined values for certain standard parameters:
AC - enabling of automatic closing : enabled
TC - setting of automatic closing time : 1 minute
C5 - step-by-step/opening command operation : step-by-step
RM - remote control operation : step-by-step
AM - AUX plug-in board operation : step-by-step
SS - Selection of automation status at start-up : closed
C0 - Predefined setting, condominium use 0
This selection loads predefined values for certain standard parameters:
AC - Enabling of automatic closure : enabled
TC - setting of automatic closing time : 1 minute
C5 - step-by-step/opening command operation : Opening
RM - remote control operation : Opening
AM - AUX plug-in board operation : Opening
SS - Selection of automation status at start-up : closed
RD - Resetting of general settings (SETTINGS RESET)
→→
→
2” 2”
AA - Activation of additional configurable parameters for each
function of the main menu.
→
2”
After activation you can scroll through the third level menus.
The third level menus are activated for 30 min.
AT - Automatic configurations