Instruction Manual

- 23 -
0DT866 10-05-2022
Display message Problem Check
Current limit exceeded Requested motor torque
exceeds available torque.
Reduce opening speed.
Check power supply.
Check power supply wiring.
Insert brake resistance Voltage on BUS exceeds
threshold
For Sector Reset doors, connect the brake resistance and set
the item on the advanced menu to "YES".
Switch o󰀨 the control panel, wait 3 minutes and reconnect the
power supply.
If the error reoccurs, check that the voltage on the BUS is lower
than 360 V.
Max. BUS voltage BUS voltage exceeds
threshold
Switch o󰀨 the control panel, wait 3 minutes and reconnect the
power supply.
Check the control panel power supply voltage.
Stand by Encoder Installation of a new control/
replacement control already
programmed previously
Absolute Encoder not
connected.
To reset the control panel follow the procedure:
• DIP2 in ON
push STOP (the control panel goes in the “programmin menu”
showing the data already set)
scroll the menù till the step “COMMAND MODE” and set LIMIT
SWITCHES
DIP2 in OFF
FUSES
ID Value Size Circuit
F1 - F2 12A - 500V 10.3 x 38 Single phase line
P5
P3 P4P1 P2
41 40 20 9 8 4 3 2 1 1 0 LAMP1 11 12 13
ON
OFF
1 2 3 4 5 6 7 8
DL
2
3
4 5
6 7
DL
M7
M4A
M5
M6
M3
BACK
M4
1 IN NC C NO
M2
J4
15
S3 S4
S5 S2
SAFETY OPEN
F2F1
230 V
50/60 Hz
GND
L N
+F -F U V W
ON
5. TROUBLESHOOTING
4. LIMIT SWITCH ADJUSTMENT
1. Set the deceleration ramps at zero (P3 - P4)
2. Set the limit switch (C) on the gearmotor so that the door stops about
200/300mm from its closure point.
3. Set the opening limit switch (A) at the opening point.
4. Set the deceleration limit switch (B) so it is triggered at about ¾ of the
opening stroke.
5. Set the opening and closure speeds using trimmers (P1) and (P2) respectively.
6. Set the trimmers of the deceleration ramps - (P3) for opening and (P4) for
closure - to ensure the door stops at its actual "open" and "closed" positions.