User Manual
- 34 -
0DT829 01-12-2021
5.1 QUADRO ELETTRONICO 49E - COLLEGAMENTI
17 14 12 11 0 0 0 1 1 2 3 4 6 8 9 20 41
17 14 12 11 0 0 0 1 1 2 3 4 6 8 9 20 41
INPUTS
Command Function Description
1
2 N.O
Automatic closing
Permanently closing the contact enables automatic closing.
1
3 N.O
Opening
With DIP1=ON the closure of the contact activates an opening operation.
Step-by-step
With DIP1=OFF the closure of the contact activates an opening or closing
operation in the following sequence: open-stop-close-open.
Note: if automatic closing is enabled, the stop is not permanent but at a
time that is set by the TC.
1
4 N.O
Closing
The closing manoeuvre starts when the contact is closed.
1
6 N.C
Reversal safety
device
Opening the safety contact triggers a reversal of the movement (reopening)
during a closing operation.
41
8 N.C
Reversal safety
device
Opening the safety contact triggers a reversal of the movement (reopening)
during a closing operation.
1
9 N.C
Stop
Opening the safety contact stops the current operation.
1
9 N.O
Non-pulse command
Permanently opening the safety contact enables the operation by non-
pulse command.
In this state, the opening (1-3/1-20) and closing (1-4) controls function only
if held in the pressed position, and the automation stops when the controls
are released.
All safety switches, the step-by-step control and the automatic closing
function are disabled.
1
20 N.O
Partial opening
The closing of the contact activates a partial opening operation of the
duration set with the RP trimmer.
Once the automation stops, the partial opening control performs the
opposite operation to the one performed before stoppage.
0
11 N.C
Closure limit switch
The opening of the limit switch contact stops the closure operation.
0
12 N.C
Opening limit switch
The opening of the limit switch contact stops the opening operation.
0
17
N.O Photocell limit switch By-pass Photocell
5.1 49E ELECTRONIC CONTROL PANEL - CONNECTIONS
Operation by non-pulse command Operation by pulse command
OUTPUTS
Output Value Description
1 +
0 –
24 V = / 0,5 A
Accessories power supply.
Power supply output for external accessories, including automation status
lamp.
0 14
24 V = / 50 W
(2 A)
Lampeggiante (FML).
Flashing signal (jumper OFF on FML).
Activated during opening and closing operations.
- LK +
24 V = / 0,5 A Output activated during the door running.
U W V
M
3 ~
400 V~ / 4 A
Three-phase motor.
Note: if the direction of rotation of the motor is incorrect for the desired direction
of movement, swap the U - W phases.
49E