8. BATTERY OPERATION
8.1 Monitoring
Discover AES reports to the Conext SCP and/or Combox as a battery monitor (BATTMON) device. The AES
batteries provide signicantly more accurate battery parameter readings than the inverters and charge
controllers are capable of.
8.2 Battery Charging
Absorption
Charge Current % of Bulk Charge C-Rate [%]
Balance
Voltage - U Current - I
Bulk
Battery Voltage [V]
44.820%
40%
60%
80%
100%
48
51.2
54.4
57.6
The charging voltage during Balance phase is a dynamic value determined by the state of all connected AES
batteries. Voltage and current values may vary between system to system.
▲ NOTE
When charging with Conext systems, AES charging
voltages may be up to 2.88V higher than specied in
published Discover Charge Algorithms.
8.3 Battery Maintenance
Batteries should be carefully inspected on a regular basis in order to detect and correct potential problems
before they can do harm. This routine should be started when the batteries are rst received.
• Look for cracks in the case
• Check the battery, terminals and connections to make sure they are clean, free of dirt, uids and corrosion
• All battery cables and their connections should be tight, intact, and NOT broken or frayed
• Replace any damaged batteries
• Replace any damaged cables
• Check torque on terminal bolts
9. RECYCLING AND DISPOSAL
Advanced Energy Systems are recyclable and must be processed through a recognized recycling agency or
dealer. Please contact Discover or your servicing dealer for details.
17
Figure 10. Smart Battery Charging Algorithm for 48V AES batteries with Conext Systems