Installation Guide

7.5 Storage
Systems should be stored out of direct sunlight in compliance with the following temperature conditions:
Minimum Storage Temperature -20°C / -4°F
Maximum Storage Temperature 45°C / 113°F
Batteries should be put into storage at 80% SOC and checked monthly to ensure the SOC does not fall below 20%.
At 20% SOC the battery will self discharge in approximately 2 months.
CAUTION!
Do not store a discharged battery. Recharge battery after every
use. Batteries that have self-discharged to a severely discharge
state are not recoverable.
8. Protection & Faults
BMS generates faults when maximum operating limits are reached.
BMS sounds a buzzer when fault limits are triggered.
BMS monitors the following information for faults and warning:
1. Cell module voltage
2. Battery current
3. Battery temperature
NOTE!
Refer to device technical specication tables at the end of this
manual for Fault Limits.
CORRECTIVE ACTIONS
High Temperature
Stop discharge or charge
Leave the battery to cool
Low Temperature Stop discharge or charge
High Voltage
If charging, stop the charge
Conrm proper charge algorithm is being used
Low Voltage
Do not discharge the battery - if any discharge current is detected, this will
force the battery into Low Voltage Fault
Charge the battery in Low Voltage Recovery - if no charge current is
detected within 2 minutes the BMS will set the battery to OFF
Over Current Reduce current
Low SOC
Stop discharge
Charge the battery
Inaccurate SOC displayed by
Power Conversion system
Battery voltage based SOC calculations provided by Power Conversion
systems do not work properly with Lithium battery voltage.
Use a Discover CAN Bus Battery Discharge Indicator (p/n 950-0005, 950-
0006, 950-0007) to display accurate SOC. To communicate accurate SOC
in a closed loop Power Conversion system use a Discover LYNK Commu-
nications Gateway device (p/n 950-0015)
10