Specifications
© Systeme Lauer GmbH & Co KG • Kelterstr.59 • 72669 Unterensingen • Tel. (07022) 96 60-0 • Fax (07022) 96 60-103
D-9
D Buep 19e-Direct driver
Other:
Timer T1 „TIMER“ is used for timeout monitoring in the PCS_KOMM
program.
INIT
Determines the initialization values of the PCS data area. Here, you
can pre-assign the interlocks for the data transfer. Allow only so much
data exchange as needed. With the exchange of fewer data, the
communica-tion speed is increased.
COFF
Determines the measures at a communication loss. The block is
executed once after a communication loss.
Attention!
Check the functioning of the handling software. The INIT and COFF blocks
must be pre-assigned for the respective PCS. The program listing shows
some examples.
D1.4 Implementation of the software
The README.DOC/PROJECT.DOC files on the PCS 91.BOS floppy disk
contain current notes concerning the use of the various projects.
Procedure:
• Equip the rack
• Set the block address on CPU and I/O boards
• Set the interface on the CPU and the SK (if possible set all to the
same parameters)
• Copy the corresponding project (e.g. BOSMULPS.500) stored on
the PCS 91.BOS floppy disk to the hard disk
• Supply voltage to the programmable controller and the I/O boards
• Run the programmable controller programming software, select the
project for the CPU, enter the configuration in the SK table and transfer
it into SK (under LOADER).
• Transfer the programmable controller program into the controller using
the loader (if necessary, link in your application program and link
newly)
• Connect PCS and programmable controller using an adapter cable
described in section 4 (are the DIL-switch segments 5 and 6 at the
PCS correspon-dingly set?). The location for attaching the adapter
cable is arbitrary. How-ever, the block address must be correct and
the communication baud rate must correspond with the PCS.
Plugging the communications cable into the addressed CPU will
increase the communication speed.