Specifications
© Systeme Lauer GmbH & Co KG • Kelterstr.59 • 72669 Unterensingen • Tel. (07022) 96 60-0 • Fax (07022) 96 60-103
C-8
C Buep 19e-Expander driver
C1.4 Board settings
Please set the segments of the switch of the ZS500 and SK500 boards
for setting the interface parameters as follows:
S6 switch
DIL12345678
ON OFF ON ON ON ON ON OFF 19200 BAUD
ON OFF ON ON OFF ON ON OFF 9600 BAUD
ON OFF ON ON ON OFF ON OFF 4800 BAUD
ON OFF ON ON ON ON OFF OFF 1200 BAUD
Please set the segments of switch 5 of the ZS500 and SK500 boards (I/
O groups in parenthesis) for setting the board address as follows:
DIL 1(7) 2(8) board
OFF OFF 0
ON OFF 1
OFF ON 2
ON ON 3
For adjustment of the transfer rate adjust the DIP-switches for the CL200
as following:
DIL 1 2 Baud
OFF OFF 9600
ON OFF 19200
OFF ON 38400
Tip!
Inspect the function of the handling software to avoid failures of the PCS
or PLC.
R200 coupling card settings Pay attention that in the CPU of the CL200 is loadrd at least the Firm-
ware version 1.5 of 06.03.1996 eingespielt ist.
On the settings of the card pay attention to the DIP-switches S1 and S2.
DIP-Switches
DS1 DS2 Protokoll
ON OFF BUEP19e-Protocol
DS3 DS4
ON ON Parity
DS5 DS6 DS7 Transfer rate
OFF OFF OFF 38 400 Baud
ON ON ON 19 200 Baud
OFF ON ON 9 600 Baud
ON OFF ON 4 800 Baud
DS8
OFF Control signals not evaluate