Specifications
© Systeme Lauer GmbH & Co KG • Kelterstr.59 • 72669 Unterensingen • Tel. (07022) 96 60-0 • Fax (07022) 96 60-103
C-3
C Buep 19e-Expander driver
Connection of the PCS to the PLC 1. Set DIL-switch 8 to „OFF“ and DIL 9 to „ON“ (on the rearside the
PCS). Set the DIL-switches 5 and 6 according to the selected baud
rate and interface. Initiate a reset of the PCS.
2. Apply operating voltage (19..33V) to the PCS. At least the ERR LED
must light now.
3. Connect the programming interface of the programmable controller
to the PCS using a suited cable.
4. Set the P2 restart input to „1“.
5. Now the ERR LED at the PCS must be deactivated. Idle text 0 is
shown on the display of the PCS.
After setting and loading the PLC corresponding to section 2, you can
connect the PCS to the PLC corresponding to the following instructions.
Attention!
Check the function of the PCS and PLC after programming or driver
installation. All parameterized functions have to be checked. Otherwise
failures of the PCS or PLC are possible.
Trouble-shooting Errors which might occur during first commissioning are listed below:
1. DIL switch 8 is set to ON. In this case, the PCS starts a diagnosis
routine after being switched on. This routine is only required for test
purposes. Remedy: Set the DIL switch to OFF and restart the PCS
(by switching it off for a short time or by shortly pressing the RESET
push-button located above the DIL switch).
2. The DIL switches 5 and 6 (interface and baud rate selection) are not
correctly set. Check the settings at the PCS using the HLP key and
arrow-down key.
3. Is the correct cable being used? This is PCS 706 for TTY (observe
the polarity) and LCA 035/235 for RS-232 (polarity not important) or
a cable as described in chapter 3.
4. Has the correct program being loaded into the programmable
controller? Does the P2 parameter indicate a „Restart after fault“?
5. In dataword 3 of the PCS datablock will be reportet an error wiith a
value different to zero. In this case the error should be searched in
the PLC-PCS connection. Possibly the cable is defect.
6. Communication is established but after a certain time the PCS
displays the following message:
======== COMMUNICATION ERROR ========
In this case, please read the following section.