B Buep 19-Expander driver
Now, the ERR LED (PCS) and the A0.0 output LED (programmable
controller) must have been deactivated. Also the 7-segment display
at the CPU must remain dark. Thus, the communication is active.
Attention!
In all projects on the floppy disk, the INIT and COFF PBs are to be adjusted
specifically for the connected operating console. The contained HLT
commands are to be deleted.
B1.4 Settings of the PLC
Please set the segments of the switch of the ZE 300/301 board as follows:
S1 switch
DIL87654321
X X X X X OFF ON ON 1200 BAUD
XXXXXONOFFON 4800 BAUD
XXXXXONONOFF 9600 BAUD
XXXXXONONON 19200 BAUD
The switch is located on the upper edge of the ZE 300/301 board. The
exact location can be taken from the „BOSCH CL300 devices manual“.
Turn shortly off the programmable controller after changing switch
positions.