B Buep 19-Expander driver
Interfaces Interface and baud rate can be selected from combinations set with the
DIL switches 5 and 6 on the rearside of the PCS 090. The choice consists
of: RS-232C or TTY, 19200, 9600, 4800, or 1200 baud. The speed of the
communication depends decisively on the baud rate (e.g. a changed va-
riable must be read 2 times!). Select only on a slower baud rate if you
have longer distances between the participants. We recommend to
communicate with 19200 baud via TTY.
The relation baud rate to maximum distance is as follows:
Baudrate max length RS-232C max. length TTY
19200 15m 150m
*)
9600 15m 300m
*)
4800 15m 350m
*)
1200 15m 350m
*)
*)
When using a shielded and twisted cable with 14 x 0,14mm, a line resistance
of less than 138 /km, and a capacity of less than 120 pF/m.
Communication data block The number of the communication data block containing the send ad
receive buffers must be passed on to the 3P90BUEP drivers. The value 0
(default value) must be entered if you do not change the communications
software in the programmable controller. The communication data block
consists of 2 times 32 data words (= 128 bytes).
Timeout time The timeout time to be set is the maximum time, the programmable con-
troller needs for the cyclical call of the PCSKOMM communication pro-
gram plus the communication time. The time is settable between 0.5 and
2.55 seconds. Time monitoring is activated only if the order read by the
PCS is not yet the current one.
Thus, the resulting timeout parameter (element x 10 ms) and the timeout
parameter P6 (Kx.1 = x 100ms) for the programmable controller without
user program is as follows:
Baudrate Timeout PCS P6 (timeout progr. contr.)
19200 50 K2.1
9600 50 K3.1
4800 50 K5.1
1200 170 K17.1
Attention!
You must add the maximum scan time to the above indicated times.
Example: 19200 baud, 800 ms maximum scan time -> timeout PCS =
130, P6 = K10.1.