A LAUER driver
The implementation is limited (besides the cyclical call of the
PCSKOMM PB) to reading of and writing to the DWs in the transfer
data block (only with default assignment!). The presence of the (selec-
table) transfer data block is not examined. It must be present in the
programmable controller with the required net length (dynamic).
Otherwise the programmable controller shows a fault (possibly only
at the first call of a present value). A general fault bit ERORX (P3)
enables the communication status to be evaluated by the ladder
diagram. The data transfer has been stopped if this fault bit is set to
1. It can be restarted by setting the RSETX (P2) flag. Furthermore,
another flag FIRSTRUX (P4) for the restart is required. This is set
after the first successful processing of the handling block. The restart
flag must be reset in start OBs (as in the example on the floppy
disk).
Customer-specific blocks (PBs) are selected at 2 positions in the PCSKOMM
block:
1: (INIT) customer-specific presetting for the communication start
2: (COFF) customer-specific assignment for the communication loss
They are to be created and/or to be extended (perhaps separately per
channel).
Attention!
These blocks are of course available on the floppy disk (common for all
channels). However, they contain only one „HLT“ command with subse-
quent examples for the corresponding PCS operating consoles.
You should delete the „HLT“ command and extend the block corresponding
to the used operating console before you execute the example. If this is
not considered, the CPU enters the STOP state with the status „1“ shown
on the display.
Scan time extension The processing time of the handling block depends on several elements.
This is for one the specification of the programmable controller scan-
time (ZV, S,.. and/or „AA“ driver parameter) in the operating console. If
the specified time is sufficiently large compared to the selected baud
rate (e.g. exceeding 500 ms at 19200 baud), all cyclical tasks of the
operating console will be contained in each data packet i.e. all tasks are
cyclically replaced. On the other hand the number of the words to be
replaced depends on the number of variables (present values) in the
display and the message words to be transferred. This number is
adjustable for some PCS operating consoles.
Control Process time/ch.
CL300 approx. 10 ms
CL400/500 approx. 650 µs
PC600 approx. 3 ms
The response is optimal if the scan time is specified sufficiently large (in
the PCS) with the -PCSKOMM PB finding a PCS 830.3/1 board ready for
data interchange in each cycle.