Specifications

© Systeme Lauer GmbH & Co KG • Kelterstr.59 • 72669 Unterensingen • Tel. (07022) 96 60-0 • Fax (07022) 96 60-103
A-13
A LAUER driver
Address assignment table The following table contains the possible address settings for the 3
channels of the PCS 830.3 (or 1 channel for the PCS 830.1). Take note,
that DIL 5 and DIL 6 must be set to OFF (logical 0) for single processor
systems (CL300, PC 600). The assignment is set to the corresponding
ZE central unit for a CL500 multi-processor system.
EZ/AZ D0W D1W D2W DIL6 DIL5 DIL4 DIL3 DIL2 DIL1 CL500, ZE:
0-3 0E02 1002 0E01 0 0 0 0 0 0 0
4-7 0E06 1006 0E05 0 0 0 0 0 1 0 D4
8-11 0E0A 100A 0E09 0 0 0 0 1 0 0 D5
12-15 0E0E 100E 0E0D 0 0 0 0 1 1 0 D6
16-19 0E12 1012 0E11 0 0 0 1 0 0 0
20-23 0E16 1016 0E15 0 0 0 1 0 1 0
24-27 0E1A 101A 0E19 0 0 0 1 1 0 0
28-31 0E1E 101E 0E1D 0 0 0 1 1 1 0
32-35 0E22 1022 0E21 0 0 1 0 0 0 0
36-39 0E26 1026 0E25 0 0 1 0 0 1 0
40-43 0E2A 102A 0E29 0 0 1 0 1 0 0
44-47 0E2E 102E 0E2D 0 0 1 0 1 1 0
48-51 0E32 1032 0E31 0 0 1 1 0 0 0
52-55 0E36 1036 0E35 0 0 1 1 0 1 0
56-59 0E3A 103A 0E39 0 0 1 1 1 0 0
60-63 0E3E 103E 0E3D 0 0 1 1 1 1 0
0-60 0EXX 10XX 0EXX 0 1 x x x x 1 *)
0-60 0EXX 10XX 0EXX 1 0 x x x x 2 *)
0-60 0EXX 10XX 0EXX 1 1 x x x x 3 *)
0: logical 0 (OFF)
1: logical 1 (ON)
x: Arbitrary setting
*): only allowed for CL500 (DIL 1..4 settings depend on the EZ/AZ
address -> refer to ZE central unit settings)
D4..D6: Factory set state and address setting as an example (channel
1..3 D4..D6)
D0..2W: RDADR/WRADR/STADR (CL300 and CL500 entries in the
QUVERWX data block)