A LAUER driver
Customer-specific presettings are to be inserted at 2 positions:
PB INIT customer specific presetting for restart
PB COFF customer specific assignment for an error case
Attention!
In all projects on the floppy disk, the INIT and COFF PBs are to be adjusted
specifically for the connected operating console. The contained HLT
commands are to be deleted.
A1.3 Parameterization of the PCSKOMM PB
P0: Cross-reference data block (here -QUERWL)
The cross-reference addresses are listed in this block. At the restart,
these addresses will be transferred once into the PCS 830. It is
ensured, that the download of the cross-reference list is made in the
first cycle of the programmable controller. In the CL 300 this first
cycle is extended due to the download by approx. 100 ms. During
the following cycles, the -PCSKOMM PB receives the corresponding
cross-reference address directly from the PCS 830 (time saving).
P1: Communication data block (here -PCSKOMM)
This block is active during processing of the handling block. Cross-
reference addresses specified in the cross-reference data block
addressing a data word relate to the here indicated data block.
P2: Switch for resetting following a fault (bit)
On a communication fault, communications can be restarted using
this bit. The faults indicated in DW3 (default assignment) are then
reset automatically! Please note that no edge evaluation is made.
I.e. with the P2 bit set, communication is automatically restarted after
a fault has appeared! This mechanism can also be realized by
connecting the P3 fault output directly to the P2 reset input.
P3: General error message (bit)
The P3 general fault bit is set for any error in the connection between
the programmable controller and the PCS 100. DW3 (default
assignment) can be evaluated for the exact cause of error. This bit is
reset as soon as the communication is running without a fault.
P4: Flag for the first processing of the handling block (bit)
This flag should be reset before the first call (restart) of the handling
block. It is automatically set during the first execution of the PB. Among
other things, it is used for presetting during a restart.
P5: Customer-specific presetting for communication start
The -INIT PB is selected at communication start. PCS-specific preset-
tings are performed by this PB. The HLT command must be removed.
P6: Customer-specific presetting for communication loss
The -COFF PB is selected at communication loss. PCS-specific
presettings are performed by this PB. The HLT command must be
removed.