Product specifications

R01AN0168ED0101 Rev. 01.01 39
Application Note
Chapter 7 Performing Zero Point Detection
Figure 7-3 Reaching the Zero Point
In the best case, the induced voltage is slightly below the selected analogue
reference level, when the ZP is reached.
If this is not the case, the reference level should be selected such, that it is by
one selection step lower than the induced voltage, even if the ZP is reached.
The remaining detection of the level in detail then has to be perfomed by using
the digital filtering features of ISM.
(3) Definition of the Measurement Window using the Blanking Time
In general, ISM provides two options (which can also be combined), to set the
timing of the measurement window: The
Blanking Time and the ZPD table
itself.
The
Blanking Time is an additional delay, which can be applied optionally after
a measurement start trigger (
ZMTn set in the ZPD table).
Using the
Blanking Time allows a delayed measurement start in a certain
range, so that the self-induction phase of the coil and other undesired noisy
phases can be skipped (blanked out).
The
Blanking Time can be defined by the setting ZBTn for each physical
channel individually. The value of
ZBTn represents the number of
Measurement Cycles
1
to wait, until the measurement phase is started.
The measurement phase then is shortened in its beginning by the
Blanking
Time
.
The following figure shows the waveform of the induced voltage, while the ZP
is not yet reached, and how the electrical parameters and delays can be set to
define the measurement window.
Zero Point not
yet reached
Zero Point
reached
Reference
Level
1)
See 7.2.2 “ZPD Measurement Cycles” for details.