Goodman AVPTC Spec Sheet ComfortBridge

14 www.goodmanmfg.com SS-GAVPTC
SS-GAVPTC www.goodmanmfg.com 15
Heat Kit Data (cont.)
Electric Heat Airflow Table
Htr
Kw
AVPTC25B14 AVPTC29B14
AVPTC29B14
AVPTC29B14
AVPTC31C14 AVPTC31C14
AVPTC37C14
AVPTC39C14
AVPTC49C14
AVPTC59C14
AVPTC37D14
AVPTC49D14
++
AVPTC59D14
AVPTC61D14
++
3 550 550 550 600 600 NR NR NR NR NR NR
5 650 650 650 700 700 700 800 870 950 990 1030
6 700 700 700 770 750 770 800 970 1060 1110 1150
8 800 800 800 880 850 880 950 1060 1150 1200 1250
10 850 850 850 970 920 970 1090 1120 1220 1240 1320
15 875 875 875 1090 950 1090 1290 1220 1520 1520 1650
19 NR NR 1050 1280 NR 1280 1345 NR NR NR NR
20 NR NR NR NR NR NR NR 1250 NR 1520 1690
21 NR NR NR NR NR NR NR NR NR NR NR
25 NR NR NR NR NR NR NR NR NR NR 1750
Selecng Heater Kit: Use the Electric Heang Waage Menu (EHt) to select heater kit size. See "Menu Navigaon and Selecon Instrucons"
above. Default selecon is 0 (No Heat Kit). Select installed heater kit for heater kit operaon.
NR - Not Rated
++ For match up with a 3 ton outdoor unit: Airow for 5kW up to 15kW heater kits shall be set to 1220 CFM by selecng 10 in the
Electric Heang Waage (EHt) menu.
+++ For match up with a 3.5 ton outdoor unit: Heater kit applicaon shall not exceed 20 kW. Airow for 5kW up to 20kW heater kits
shall be set to 1320 CFM by selecng 10 in the Electric Heang Waage (EHt) menu.