Heat Kit Data (cont.)
Heater Kit Model
Circuit 1 Circuit 2 Single-Point Kit
Heater
Amps
MCA¹ MOP² Heater Amps MCA¹ MOP² MCA¹ MOP²
HKSC05XC - 208 V
Breaker
17.3 30.3 35 --- --- --- --- ---
HKSC08XC - 208 V 28.9 45 45 --- --- --- --- ---
HKSC10XC - 208 V 34.7 52 60 --- --- --- --- ---
HKSC15XB
3
- 208 V 34.7 52 60 17.3 21.7 25 73.6 80
HKSC20DH - 208 V 34.7 52 60 34.7 43.3 45 95.3 100
HKSC15XF - 208 V ^ 0 8.6 15 30 37.5 40 --- ---
HKSC20XF - 208 V ^ 0 8.6 15 37.5 47 50 --- ---
HKSC25DA - 208 V 52 73.6 80 34.7 43.3 45 117 125
HKSX03XC - 240 V
No Breaker
--- --- --- --- --- --- --- ---
HKSX05XC - 240 V 20 34 35 --- --- --- --- ---
HKSX06XC - 240 V 25 39.9 40 --- --- --- --- ---
HKSX08XC - 240 V 33.3 50.3 60 --- --- --- --- ---
HKSX10XC - 240 V 40 58.6 60 --- --- --- --- ---
HKSC05XC - 240 V
Breaker
20 34 35 --- --- --- --- ---
HKSC08XC - 240 V 33.3 50.3 60 --- --- --- --- ---
HKSC10XC - 240 V 40 58.6 60 --- --- --- --- ---
HKSC15XB - 240 V 40 58.6 60 20 25 25 83.6 90
HKSC20DB - 240 V 40 58.6 60 40 50 50 108.6 110
HKSC15XF - 240 V ^ 0 8.6 15 34.6 43 45 --- ---
HKSC20XF - 240 V ^ 0 8.6 15 43 54 60 --- ---
HKSC25DB - 240 V 60 84 90 40 50 50 133.6 150
¹ Minimum Circuit Ampacity (Heater Amps + Motor Amps) X 1.25
² Maximum Overcurrent Protecon = 2.25 X Motor Amps + Heater Amps
^ Circuit 1: Single-phase for Air Handlers Circuit 2: Three-phase for HKR3 Heater Kits
Note: The 208 or 240 in the heat kit part number eld is for claricaon of the nominal voltage for this model.
3
Notaon is correct as XB because technically the 240V heater kit applicaon can be used here without any issues.