Technical data

4
Dimensions
A
B C D
E
5
TH
port for recirculation defrost type models only
0
0.2
0.4
0.6
0.8
1
1.2
0
50
100
150
200
250
300
400 80
SHR(D) 1505R
SHR(D) 2005R
120 160
Airflow (cfm)
Airflow (L/s)
Static Pressure (in WC)
Static Pressure (Pa)
200 240
190 38 57 76 94 114
Fresh Air
From Outside
Stale Air
To Outside
Fresh Air
To Inside
Stale Air
From Inside
5
TH
port for recirculation defrost models
only can be ducted or left open
Airflow
PHRVR 160 & PHRVR 210 Series HRV
Model A B C D E
PHRVR 160 2
1
/4" (56mm) 23
1
/2" (596mm) 2
5
/8" (67mm) 17
3
/8" (441mm) 17
3
/8" (441mm)
PHRVR 210 2
1
/4" (56mm) 27
7
/8" (707mm) 2
5
/8" (67mm) 17
3
/8" (441mm) 20
1
/2" (520mm)
Fan Performance
Performance Data
Model
PHRVR 160 72 % 69 %
PHRVR 210 71 % 76 %
Apparent Sensible
Effectiveness at
32ºF (0ºC)
Apparent Sensible
Effectiveness at
-13ºF (-25ºC)
AIRFLOW CAP. cfm (L/s) @ 0.4 on High Speed
Power
• Volts 120 VAC
• Amperage
PHRVR 160 1.5 Amps Total
PHRVR 210 1.9 Amps Total
• Phase Single Phase
6"
PHRVR 210
PHRVR 160