Specifications

DCP2010 Control Settings – Rural Electric Cooperatives Appendix A
DCP2010 Control Settings - Rural Electric Cooperatives
This is a simplified document for trained contractors. For complete instructions, please refer to
the DCP2010 Installation and Operating Instructions
a) Setting the DIP Switches. The DIP switches are located
on the PCB board within the enclosure.
Position
Set Switch Description
8 OFF
Rate Signaling, Closed contact for
Off-Peak
NOTE: this DIP Switch must be changed to “ON” if the Utility
uses an open contact for Off-Peak times
b) Setting the Charge Controller – Operator Mode. Installer to set.
Selection
Enter Set
Points
Uhr:
Ja, set time Timer (Ja =YES) Set time based on a 24h-Clock
TAE:
Day
Setting the day: T1=Monday, T2=Tuesday, T3=Wednesday,
T4=Thursday, T5=Friday, T6=Saturday, T7=Sunday
ANZ
AU Real-Time display
c) Setting the Charge Controller – Technician Mode
To set in Technician mode, press the black button as shown
on the right. The red LED will illuminate.
In Technician Mode, installers must set the following based on
the length of the Utility’s Off-Peak period.
Selection
8hr (Off-Peak)
Enter Set Points
10hr (Off-Peak)
Enter Set Points
12hr (Off-Peak)
Enter Set Points
Description
E1 -24 -24 -24 Full charge setting
E3 7 h 9h 11h Main charge duration
TU: 9 h 11h 13h
SEH 0 h 0 h 0 h
All other settings to be left at factory defaults.
After these selections, press button to de-select Technician Mode. Red LED will turn off.
If Mid-Peak rates are available, please contract Dimplex @ 1-800-668-6663 x339.
NOTE. Installer to fill out the following commissioning table and leave with the
homeowner for their records.
WARNING:
Ensure all circuits are de-
energized before opening
control enclosure as there
may be up to five live
circuits