SI 24TE - SI 37TE
12 Equipment Data
1 Type and order code
SI 24TE SI 30TE SI 37TE
2Design
2.1 Degree of protection according to EN 60 529 IP 21 IP 21 IP 21
2.2 Installation location Indoors Indoors Indoors
3 Performance data
3.1 Operating temperature limits:
Heating water flow °C up to 58 ± 2 up to 58 ± 2 up to 58 ± 2
Brine (heat source) °C -5 to +25 -5 to +25 -5 to +25
Antifreeze Monoethylene glycol Monoethylene glycol Monoethylene glycol
Minimum brine concentration (-13 °C freezing temperature) 25% 25% 25%
3.2 Temperature spread of heating water
(flow/return flow) at B0 / W35
1
K
1. Operation with 2 compressors.
9.4 5.0 10.0 5.2 10.0 5.0
3.3 Heat output / COP at B-5 / W55
2
kW / ---
1
2. This data indicates the size and capacity of the system according to EN 255 or EN 14511. For an analysis of the economic and energy efficiency of the system, both the bivalence
point and the regulation should also be taken into consideration. The specified values, e.g. B10 / W55, have the following meaning: Heat source temperature 10 °C and heating
water flow temperature 55 °C.
19.7 / 2.3 24.7 / 2.4 28.9 / 2.4
kW / ---
3
3. Operation with 1 compressor.
9.3 / 2.1 9.0 / 1.7 12.1 / 2.2
at B0 / W45
2
kW / ---
1
22.3 / 3.1 28.7 / 3.3 33.0 / 3.2
kW / ---
3
11.3 / 3.1 12.0 / 2.7 13.4 / 2.7
at B0 / W50
2
kW / ---
1
22.7 / 2.9 28.1 / 2.9 34.3 / 3.1
kW / ---
3
10.8 / 2.7 11.3 / 2.4 13.1 / 2.4
at B0 / W35
2
kW / ---
1
24.0 / 4.3 23.7 / 4.1 31.2 / 4.6 30.3 / 4.4 37.2 / 4.6 35.4 / 4.3
kW / ---
3
12.5 / 4.4 12.7 / 4.3 14.4 / 4.2 14.1 / 4.1 17.0 / 4.2 18.3 / 4.4
3.4 Sound power level dB(A) 59 62 63
3.5 Sound pressure level at a distance of 1 m dB(A) 43 46 47
3.6 Heating water flow with an internal pressure differential of m³/h / Pa
2.2
4
/ 3100
4. Minimum heating water flow rate
4.0
5
/ 9800
5. Recommended heating water flow rate and brine throughput
2.6
4
/ 1100 5.0
5
/ 2500 3.2
4
/ 1650 6.0
5
/ 5100
3.7 Brine throughput with an internal pressure differential
(heat source) of m³/h / Pa
5.6
5
/13000 5.6
5
/13000 7.0
5
/6000 7.0
5
/6000 8.5
5
/10000 8.5
5
/10000
3.8 Refrigerant; total filling weight type / kg R404A / 3.7 R404A / 7.7 R404A / 6.8
3.9 Lubricant; total filling weight type / litres
Polyolester
(POE) / 2.72
Polyolester
(POE) / 3.54
Polyolester
(POE) / 3.9
4 Dimensions, connections and weight
4.1 Device dimensions without connections
6
H x W x L mm
6. Note that additional space is required for pipe connections, operation and maintenance.
1660 x 1000 x 775 1660 x 1000 x 775 1660 x 1000 x 775
4.2 Device connections to heating system Inch
G 1 1/4'' internal/exter-
nal
G 1 1/2'' internal/exter-
nal
G 1 1/4'' internal/exter-
nal
4.3 Device connections to heat source Inch
G 1 1/2'' internal/exter-
nal
G 2'' internal/external G 2'' internal/external
4.4 Weight of the transportable unit(s) incl. packing kg 282 365 371
5 Electrical connection
5.1 Nominal voltage; fuse protection V / A 400 / 20 400 / 20 400 / 20
5.2 Nominal power consumption
1
B0 W35 kW
5.61 5.81 6.78 6.91 8.04 8.26
5.3 Starting current with soft starter A 20 25 26
5.4 Nominal current B0 W35 / cos ϕ
2
A / ---
10.12 / 0.8 10.48 / 0.8 12.23 / 0.8 12.72 / 0.8 14.51 / 0.8 14.90 / 0.8
5.5 max. power consumption of compressor protection
(per compressor) W
70 70 70
6 Complies with the European safety regulations
7
7. See CE declaration of conformity
77
7 Additional model features
7.1 Water in device protected against freezing
8
8. The heat circulating pump and the heat pump manager must always be ready for operation.
Yes Yes Yes
7.2 Performance levels 2 2 2
7.3 Controller internal/external Internal Internal Internal