Technical data

90 | Project planning manual for heat pumps for heating and domestic hot water preparation | 01.2012 www.dimplex.de
7.7 Heat pump manager
7.7 Connection of external system components to the heat pump manager
Inputs
* EconPlus
Outputs
With the WPM 2006 plus, the remote fault indicator and the swimming
pool pump are connected via the RBG WPM relay module which is avail-
able as a special accessory.
7.8 Technical data for the heat pump manager
Compliance with utility requirements
Switch-on delay when supply voltage is recovered or utility
shut-off time is lifted (10 s to 200 s)
The heat pump compressors are switched on a maximum of
three times per hour.
Heat pump is switched off by the utility blocking signal with
the option of switching on the second heat generator .
General
Self-adjusting defrosting cycle time
Monitoring and fusing equipment of the refrigerating cycle
according to DIN 8901 and DIN EN 378
Identification of the respective optimum mode of operation
with the largest possible heat pump proportion
Frost protection function
Low pressure switch brine for installation in the brine circuit (spe-
cial accessory)
WPM ECONPLUS
Integrated thermal energy metering with sensors in the refriger-
ating circuit
Connection Explanation
J2-B1 X3-R1* X3 External sensor
J2-B2 R2.1* X3 Return sensor
J2-B3 R3* X3 Domestic hot water sensor
J3-B5 X3 Flow sensor (antifreeze)
J6-B6 X3-R5* J6-GND Sensor, heating circuit 2
J6-B8 X3-R13* J6-GND Sensor, heating circuit 3
J5-ID1 X2 Domestic hot water thermostat
J5-ID2 X2 Swimming pool thermostat
J5-ID3 X2 Utility block
J5-ID4 X2 External disable contact
J5-ID5 X2 Primary pump / fan fault
J5-ID6 X2 Compressor fault
J7-ID9 X2 Low pressure brine
J7-ID12 X3-N20.1 X3 External thermal energy meter 1
J20-ID17 X3 Circulation system requirements
J20-ID18 X3-N20.1 X3 External thermal energy meter 2
Connection Explanation
J12-NO3 N / PE Primary pump / fan
J13-NO4 N / PE 2nd heat generator
J13-NO5 X2-M13* N / PE Heat circulating pump
J13-NO6 M18* N / PE Domestic hot water circulating pump
J14-NO7 N / PE Mixer open
J15-NO8 N / PE Mixer closed
J16-NO9 X2-M16* N / PE Auxiliary circulating pump
J16-NO10 K21* N / PE Flange heater domestic hot water
J16-NO11 N / PE
Heat circulating pump for heating cir-
cuit 2
J17-NO12 N / PE Mixer open - heating circuit 2
J18-NO13 N / PE Mixer closed - heating circuit 2
J4-Y2 J22-NO17* X2 Remote fault indicator
J4-Y3 J22-NO16* Swimming pool circulating pump
- J22-N018 Circulation pump
Line voltage 230 V AC 50 Hz
Voltage range 195 to 253V AC
Power consumption Approx. 14 VA
Degree of protection according to EN 60529; protection
class according to EN 60730
IP 20
Switching capacity of outputs Max. 2 A (2 A) cos (ϕ) = 0.4 at 230 V
Operating temperature 0 °C to 35 °C
Storage temperature -15 °C to +60 °C
Weight 4,100 g
Party setting range Standard time 0 – 72 hours
Vacation setting range Standard time 0 – 150 days
Temperature measuring ranges
External wall temperature -20 °C to +80 °C
Return temperature -20 °C to +80 °C
Frost protection sensor (flow temperature) -20 °C to +80 °C
Heating controller setting ranges Limit temperature boiler release -20 °C to +20 °C
Maximum return temperature +20 °C to +70 °C
Warmer/colder +5 °C to +35 °C
Hysteresis/neutral zone +0.5 °C to +5.0 °C
Setting range
Lower operation / raise operation
Warmer/colder +5 °C to +35 °C
Setting range
Domestic hot water basic temperature
Set temperature +30 °C to +55 °C
Setting range
Domestic hot water reheating
Set temperature +30 °C to +80 °C
Mixer setting range Mixer runtime 1-6 minutes