Technical data
www.dimplex.de 01.2012 | Project planning manual for heat pumps for heating and domestic hot water preparation | 89
Heat pump manager 7.6.7
7.6.7 Heat pump manager terminal assignment
N1 Heating controller
N1-J1 Power supply (24V AC / 50 Hz)
N1-J2-B1 Outside temperature sensor - R1
N1-J2-B2 Return temperature sensor - R2
N1-J2-B3 Domestic hot water temperature sensor - R3
N1-J3-B4 Coding - R7
N1-J3-B5 Flow- or frost protection temperature sensor heating - R9
N1-J4-Y1 Defrosting
N1-J4-Y2 Fault indicator lamp - H5 via K11
N1-J4-Y3 Swimming pool water circulating pump - M19 via K12
N1-J5-ID1 Domestic hot water thermostat - B3
N1-J5-ID2 Swimming pool water thermostat - B4
N1-J5-ID3 Utility company block
N1-J5-ID4 Block
N1-J5-ID5 Fan / primary pump fault - M2 / M11
N1-J5-ID6 Compressor fault - M1 / M3
N1-J5-ID8 Flow rate switch (cooling operation)
N1-J5-ID7 Defrost end pressure switch - E3; brine limit protection - pressure switch - F6
N1-J6-B6 Temperature sensor heating circuit 2/defrost end temperature sensor - R5
N1-J6-B7 Brine limit protection sensor - R6; defrost end sensor - R12
N1-J6-B8 Frost protection sensor, cooling - R8; sensor for heating circuit 3 /
renewable sensor - R13
N1-J7-ID9 Low pressure switch brine - B2
N1-J7-ID10 Hot gas thermostat - F7
N1-J7-ID11 Switching protocol TAE
N1-J8-ID13H High pressure switch - 230V AC - F4
N1-J8-ID13 High pressure switch - 24V AC - F4
N1-J8-ID14 Low pressure switch - 24V AC - F5
N1-J8-ID14H Low pressure switch - 230V AC - F5
N1-J10 Remote control - N10 / control panel - N14
N1-J11 Connection for pLAN
N1-J12-NO1 Compressor 1 - M1
N1-J13-NO2 Compressor 2 - M3
N1-J13-NO3 Primary circulation pump - M11 / fan - M2
N1-J13-NO4 2nd heat generator (E10)
N1-J13-NO5 Heat circulating pump - M13
N1-J13-NO6 Domestic hot water circulating pump - M18
N1-J14/J15-NO7/N08 Mixer open/closed - heating circuit 3 - M21
N1-J16-NO9 Auxiliary circulating pump - M16
N1-J16-NO10 Flange heater domestic hot water - E9
N1-J16-NO11 Heat circulating pump of heating circuit 2 - M15
N1-J17/J18-NO12/NO13 Mixer open/closed - heating circuit 2 - M22
N1-J20-B9
N17.4 "Solar" module (WPM Econ SOL)
N17.1-J5-NO1 Solar circulating pump - M23
N17.1-J9-B1 Solar cylinder sensor - R22
N17.1-J10-B4 Collector sensor - R23
* Optional, to be supplied by the customer