Integration of the heat pump in the heating system 8.4.1
8.4.1 Compact manifold KPV 25
The compact manifold functions like an interface between the
heat pump, the heating distribution system, the buffer tank and,
in some cases, even the domestic hot water cylinder.
A compact system is used to simplify the installation process, so
that a lot of different components do not have to be installed indi-
vidually.
NOTE
The use of the compact manifold KPV 25 with overflow valve is recom-
mended for heating systems with panel heating and a heating water flow
rate up to max. 1.3 m
3
/h.
Fig. 8.6: Compact manifold KPV 25 with manifold bar VTB 25 and domestic
hot water module WWM 25
Fig. 8.7: Integration of the compact manifold for heating operation and do-
mestic hot water preparation
Fig. 8.8: Pressure drop KPV 25 depending on the volume flow
1
Mounting position of heat
circulating pump
(not included in scope of
supply)
2 Overflow valve
3
Buffer tank connections
1” internal thread
4
Heat pump connections
1” internal thread
5
Heating connections
1” internal thread
6
Expansion vessel connec-
tion ¾” external thread
7
Domestic hot water heating
connections
1” external thread
8
Immersion sleeve for
return sensor incl.
plastic retainer
9
Safety valve
¾” internal thread
10 Stop-cocks
11 Stop-cock with check valve
12 Thermometer
13 Shell insulation
KPV 25 WWM 25
VTB 25






Immersion heater
Immersion heater
Domestic hot water cylinders
Expansion vessel
Buffer tank
0,50
0,45
0,40
0,35
0,30
0,25
0,20
0,15
0,10
0,05
0,00
0,00 0,50 1,00 1,50 2,00 2,50 3,00 3,50
Volume flow (m
3
/h)
Pressure drop [bar]