Technical data
www.dimplex.de/en
90
2010
Hot-air curtain
Connection voltage 1/N/PE ~230 V, 50 Hz
Degree of protection IP 20
Protection class l
Air Curtains AC...N series
Electric operation
AC ... N
Mounting above doors or on ceilings, adjustable air output direction, 2 heating levels, 1 cold air level. Controllable on the device itself
or with a remote control (only AC 3RN) only. Door width covered adjustable from 600 mm (AC 3 and AC 45) to 900 mm (AC 6).
Order reference Art.-Nr. Rated power
W
Air volume flow
m3/h
Max. tempera-
ture increase
K
Sound pressure
level in 3 m
dB (A)
Width x Height
x Depth
mm
Weight
kg
AC 3 N 348220
3000 212 42 50
605 x 214 x 135
5.1
AC 45 N 348230
4500 248 53 52 5.2
AC 6 N 348240
6000 446 40 57 905 x 214 x 135 7.2
AC 3 RN 348250
3000 212 42 50 605 x 214 x 135 5.3
AC 3 N 348220 4015627348226
AC 45 N 348230 4015627348233
AC 6 N 348240 4015627348240
AC 3 RN 348250 4015627348257
Connection voltage 3/N/PE ~400 V, 50 Hz
Protection class l
Air barrier CAB series
Electric operation
CAB 10 E V2
Mounting above doors, ceilings or hidden (optional installation kit needed), modular design allows simple placing of devices in a row,
adjustable direction of flow, 2 heating levels, cold air level, 2 ventilation levels, controllable using wall-mounted low-voltage control or
by connecting to a building management system. A separate control panel allows regulation of up to 10 devices at a time, optional door
sensor switching. Essential accessories: CAB C5 controlsAccessories for combining up to 4 devices: connection set CAB M1 V2;
Colour white, intake grid black
Order reference Art.-Nr. Rated power
W
Air volume flow
m3/h
Max. tempera-
ture increase
K
Sound pressure
level in 3 m
dB (A)
Width x Height
x Depth
mm
Weight
kg
CAB 10E V2 117984
9000 1200
4 4
54 1057 x 262 x 316 25
CAB 15E V2 117991
13500 1800 55 1557 x 262 x 316 36
CAB 10E V2 117984 5011139117984
CAB 15E V2 117991 5011139117991
Connection voltage 3/N/PE ~400 V, 50 Hz
Protection class l
Air barrier DAB series
Electric operation
DAB 10 E V2
Mounting above doors, ceilings or hidden (optional installation kit needed), modular design allows simple placing of devices in a row,
adjustable direction of flow, 2 heating levels, cold air level, 2 ventilation levels, controllable using wall-mounted low-voltage control or
by connecting to a building management system. A separate control panel allows regulation of up to 10 devices at a time, optional door
sensor switching. Essential accessories: CAB C5 controls. Accessories for combining up to 4 devices: connection set CAB M1 V2;
Colour white, intake grid black
Order reference Art.-Nr. Rated power
W
Air volume flow
m3/h
Max. tempera-
ture increase
K
Sound pressure
level in 3 m
dB (A)
Width x Height
x Depth
mm
Weight
kg
DAB 10E V2 118004
12000 3000 23 58 1060 x 360 x 390 39
DAB 15E V2 118011
18000 4000 26 59 1560 x 360 x 390 50
DAB 10E V2 118004 5011139118004
DAB 15E V2 118011 5011139118011
Connection voltage 1/N/PE ~230 V, 50 Hz
Protection class l
Air barrier CAB series
hot water operation
CAB 10 W V2
DHW operation, mounting above doors, on ceilings or hidden (optional installation kit needed), modular design allows simple placing of
devices in a row, mounting height up to 2. 7 m, adjustable direction of flow, 2 ventilator levels, controllable using wall-mounted low-
voltage control or by connecting to a building management system. A separate control panel allows regulation of up to 10 devices at a
time, optional door sensor switching. BEAB certification Essential accessories: CAB C 6 operator control; for combining several CAB M1 V2
devices. The connections between the operator panel and the hot-air curtains and between the devices are established using a standard
data cable (type CAT 5 or higher) – data cable not included in the scope of supply!
Colour white, intake grid black
Order reference Art.-Nr. Rated power
W
Air volume flow
m3/h
Max. tempera-
ture increase
K
Sound pressure
level in 3 m
dB (A)
Width x Height
x Depth
mm
Weight
kg
CAB 10W V2 118028
8500 1100 23 53 1057 x 262 x 316 25
CAB 15W V2 118035
12700 1700 22 54 1557 x 262 x 316 36
Rated output at 20 °C air intake temperature Rated output at 80 °C flow temperature and 60°C return flow temperature
CAB 10W V2 118028 5011139118028
CAB 15W V2 118035 5011139118035